BFM Assignment 7
7-9
FX
2N
-1RM-E-SET Programmable Cam Switch
<BFM #100: Written on angle, BFM #101: Written off angle, BFM #102: Written BFM No>
The data of the turning on angle and the turning off angle can be indirectly set from a PLC main
unit to two or more outputs of FX
2N
-1RM.
(It is a function added from version V2.00)
After the turning on angle and the turning off angle data are written in BFM #100, #101, the BFM
number which wants to be written is written BFM #102. The turning on angle data of BFM #100 is
written in the BFM number specified by BFM #102 by this work. The off angle data of BFM #101
is written in the old number which continues to the specified number.
(Give setting BFM #102 as a number allocated to output on angle setting of BFM #1000 to
#7142. Refer to BFM No. Quick Reference Table for Angle setting in the end of a book.)
When the to instruction to BFM #102 is executed, the turning on angle and the turning off angle
are written.
<BFM #103:Reading BFM No., BFM #104: Reading on angle, BFM #105: Reading off angle>
The data of the turning on angle and the turning off angle can be indirectly read from a PLC main
unit to two or more outputs of FX
2N
-1RM.
(It is a function added from version V2.00)
The BFM number which wants to be read to BFM #103 is written.
Then, output on angle data of the specified BFM number is read to BFM #104.
The turning off angle data allocated to BFM of the old number which continues to the specified
number is read to BFM #105.
(Give setting BFM #103 as a number allocated to output on angle setting of BFM #1000 to
#7142. Refer to BFM No. Quick Reference Table for Angle setting in the end of a book.)
When the to instruction to BFM #103 is executed, the angle data is read to BFM #104, #105.
<BFM #106:Data transfer destination of current angle transfer function>
When the current angle transfer function is used, the current angle of the resolver is transferred
to BFM#106 via turning ON (OFF
→
ON) input terminal B1.
When neither turning ON the power supply nor the current angle transfer function are used, “-1”
is stored. (Function has been included since version V2.40)
< Application operation (FNC function) >
When using a function with FNC (FNC 70 to 75, 90), write the FNC No. to be used added to 1000
(K1070 for FNC 70, for example) to the bank No., STEP0 of the output No. and the BFM No.
(BFM #1000, BFM #1016, BFM #6376, etc.) of the ON angle to be used.
Содержание MELSEC-F FX2N-1RM-E-SET
Страница 1: ...USER S MANUAL FX2N 1RM E SET PROGRAMMABLE CAM SWITCH...
Страница 6: ...iv FX2N 1RM E SET Programmable Cam Switch...
Страница 12: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 28: ...Introduction 1 1 16 FX2N 1RM E SET Programmable Cam Switch Memo...
Страница 30: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 36: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 42: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 46: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 50: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 64: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 80: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 112: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 114: ...Monitor 9 9 2 FX2N 1RM E SET Programmable Cam Switch Memo...
Страница 116: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 124: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 128: ...FX2N 1RM E SET Programmable Cam Switch...
Страница 138: ...FX2N 1RM E SET Programmable Cam Switch Appendix A 10 Memo...
Страница 139: ...FX2N 1RM E SET Programmable Cam Switch...