Program Operating Procedures 8

8-23

FX

2N

-1RM-E-SET Programmable Cam Switch

8.3.10

Batch addition/subtraction of the output set angle [FNC60, 61]

Add or subtract a specified angle to/from all the steps of a specified output at a time (ON angle
and OFF angle) except the fixed output patterns automatically generated by FNC70 to FNC75. 

[Power ON] [PRG mode]

BANK

0

OUT

0

STEP

0

DEG

# # #

*1

ON LED

Lit

OFF LED

Exting-
uished

< Key operation >

●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●

< Display >

*1   The ON angle of the output Y00 already
      registered is displayed.

0

BANK

A

OUT

dd

STEP

0

DEG

"000"

flashes

ON LED

Exting-
uished

OFF LED

Exting-
uished

GO

BANK

2

0

GO

OUT

6

0

FNC

GO

"123" flashes on the DEG.

GO

  Batch addition [FNC60]

Specify the output No. to be
shifted.

Enter the angle to be added.

BANK

0

OUT

0

STEP

0

DEG

# # #

*2

ON LED

Lit

OFF LED

Exting-
uished

*2   When setting is finished, flashing of data
      on the DEG is changed into display of a
      value shifted.

3

1

BANK

0

OUT

0

STEP

0

DEG

# # #

*1

ON LED

Lit

OFF LED

Exting-
uished

< Key operation >

●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●●

< Display >

*1   The ON angle of the output Y00 already
      registered is displayed.

0

BANK

S

OUT

ub

STEP

0

DEG

"000"

flashes

ON LED

Exting-

uished

OFF LED

Exting-
uished

GO

BANK

2

0

GO

OUT

6

1

FNC

GO

"123" flashes on the DEG.

GO

  Batch subtraction [FNC61]

Specify the output No. to be
shifted.

Enter the angle to be
subtracted.

BANK

0

OUT

0

STEP

0

DEG

# # #

*2

ON LED

Lit

OFF LED

Exting-
uished

*2   When setting is finished, flashing of data
      on the DEG is changed into display of a
      value shifted.

3

1

Содержание MELSEC-F FX2N-1RM-E-SET

Страница 1: ...USER S MANUAL FX2N 1RM E SET PROGRAMMABLE CAM SWITCH...

Страница 2: ...ks as well as details of instructions refer to the corresponding Hardware manuals and programming manuals offered separately If in doubt at any stage of the installation of Programmable Cam Switch FX2...

Страница 3: ...i FX2N 1RM E SET Programmable Cam Switch Programmable Cam Switch FX2N 1RM E SET USER S MANUAL Manual number JY992D71101 Manual revision F Date April 2003...

Страница 4: ...OS and Windows are registered trademarks of Microsoft Corporation IBM and AT are registered trademarks of International Business Machines Corporation All other brand and product names are trademarks o...

Страница 5: ...in 34 93 589 1579 United Kingdom 01707 278 695 Please tick the box of your choice What condition did the manual arrive in Good Minor damage Unusable Will you be using a folder to store the manual Yes...

Страница 6: ...iv FX2N 1RM E SET Programmable Cam Switch...

Страница 7: ...actices c All operators of the completed equipment see Note should be trained to use this product in a safe manner in compliance to established safety practices The operators should also be familiar w...

Страница 8: ...is equipment All examples and diagrams shown in this manual are intended only as an aid to understanding the text not to guarantee operation Mitsubishi Electric will accept no responsibility for actua...

Страница 9: ...lver specifications 3 3 3 4 Power supply specifications 3 4 3 5 Input specifications 3 4 4 External Wiring 4 1 4 1 Wiring of the power supply and the input 4 1 5 Extension Block Specifications and Ext...

Страница 10: ...function FNC4 13 to 26 8 15 8 3 6 Individual automatic angle advance function FNC5 90 8 17 8 3 7 Prohibition of RUN to PRG operation FNC6 8 21 8 3 8 Current angle transfer function FNC7 8 21 8 3 9 In...

Страница 11: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 12: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 13: ...programmable controller hereinafter referred to as PLC Refer to Paragraph 1 5 for details 3 When transistor output extension blocks for the FX2N are connected up to 48 points of non contact outputs ar...

Страница 14: ...Introduction 1 1 2 FX2N 1RM E SET Programmable Cam Switch Mechanical cam operated switch 48 step cam disc 8 teeth maximum disc 48 limit switches 1 switch disc...

Страница 15: ...the data setting panel is removed 1 Mounting hole in 2 positions 2 4 5 1 77 2 Connector to connect resolver 3 STEP output pattern display 4 BANK program No display 5 OUT output No display 6 Operation...

Страница 16: ...Resolver F2 720RSV 5000 196 85 54 2 13 38 1 50 50 1 97 19 0 75 9 0 35 31 1 22 5000 196 85 54 2 13 54 2 13 28 1 10 9 0 35 31 1 22 45 1 77 45 1 77 9 5 0 37 9 5 0 37 33 32 1 31 10 0 39 60 2 36 28 1 10 4...

Страница 17: ...e FX2N 1RM They are not recognized by the PLC main unit and not included in the number of I O points 256 points maximum of the FX2N PLC Octal numbers are assigned as output Nos of the extension blocks...

Страница 18: ...connected data information and bit information can be read and written in only the FX2N 1RM unit nearest to the PLC main unit using FROM TO instructions directly given by the PLC main unit In the sec...

Страница 19: ...are assigned as output Nos from the extension block nearest to the FX2N 1RM Y00 to Y07 Y10 to Y17 Y50 to Y57 Only extension blocks with dedicated output are allowed to be connected to the FX2N 1RM If...

Страница 20: ...CL and master unit 0 1 2 3 4 5 6 7 8 9 GO ON OFF CLR RUN ERR ON OFF BANK OUT DEG STEP STEP OUT BANK FNC DEL TEACH ADJ COPY RUN STOP FX2N 1RM POWER FX2N 32CCL LRUNE LERRE RDE SD FX2N 32CCL When one FX2...

Страница 21: ...O M 3 Y 1 0 Y 1 1 Y 1 2 Y 1 3 Y 1 Y 2 Y 3 Y 1 4 Y 1 5 X 3 X 2 X 1 P O W E R B A T T V R U N C P U E P R O G E 1 O U T 0 7 2 3 4 5 6 P O W E R 1 O U T 0 7 2 3 4 5 6 0 1 2 3 4 5 6 7 8 9 G O O N O F F C...

Страница 22: ...hen the signal cable is not long enough relay cables can be connected for extension as shown in the figure above Two or more relay cables can be used The maximum extension length is 100 m 3937 inch Re...

Страница 23: ...pment Data setting panel This panel allows data setting data read monitoring copy between banks teaching and fine adjustment in the RUN mode Data setting panel When removing the data setting panel pre...

Страница 24: ...omputer A personal computer allows save and transfer of programs F X Personal computer FX 422CAB0 FX 232AW FX 232AWC Applicable software FX PCS WIN E GX Developer compatible with FX2N F2 232CAB 1 Use...

Страница 25: ...Switch Introduction 1 1 13 FX 20P E The FX 20P E allows the save and transfer of programs Use the FX 20P RWM and a memory cassette to save programs FX 20P E compatible with FX2N FX EPROM 8 FX EEPROM 8...

Страница 26: ...rred from a personal computer or the FX 20P E D1000 to D7143 correspond to BFM 1000 to BFM 7143 D7144 to D7145 correspond to BFM 0 to BFM 1 and D7146 to D7159 correspond to BFM 13 to BFM 26 At this ti...

Страница 27: ...ersions for personal computers and the FX 20P E Peripheral equipment FX2N 1RM V 2 20 or earlier V 2 30 or later FX PCS WIN E V 1 00 to V 2 11 applicable FX PCS WIN E V 3 00 or later not applicable app...

Страница 28: ...Introduction 1 1 16 FX2N 1RM E SET Programmable Cam Switch Memo...

Страница 29: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 30: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 31: ...e M3 6 2mm 0 24inch or less 6 2mm 0 24inch or less Use crimp style terminals of the size shown on the left The terminal tightening torque should be 0 5 to 0 8 N m Tighten terminals securely so that ma...

Страница 32: ...Coupling Screw M4 35 1 38 10 0 39 10 0 39 10 0 39 0 1 0 004 or less 22 0 87 10 0 39 1 30 1 3 degrees or less Resolver Coupling 50 1 97 Enlarged view of coupling Unit mm inch Manufacturer name Series n...

Страница 33: ...ettes are not connected correctly malfunction may occur caused by imperfect contact Cautions on wiring Make sure to shut down all the phases of the power supply outside the PLC before starting the ins...

Страница 34: ...line and the signal output line of the PLC together with other power lines and output lines When the cautions above are observed no problem should be expected with regard to noise even if the input ou...

Страница 35: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 36: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 37: ...d an abnormality by the self diagnosis function such as a watchdog timer error all the outputs are turned off When an abnormality has occurred in the I O control area etc which cannot be detected by t...

Страница 38: ...sistance In conformance to JIS C9012 10 G 3 times in each of three directions Noise resistance Noise withstand voltage 1000 Vp p noise amplitude 1 s by noise simulator Withstand voltage 500 VAC 1 minu...

Страница 39: ...n is used response speed becomes 207r min 0 5degree or 415r min degree Number of program banks 8 banks specified by PLC or 4 banks specified by external input Setting unit Dedicated data setting unit...

Страница 40: ...ion 3 W when operating individually 5 W at 32 points output ON In rush current 300 mA when operating individually 400 mA at 32 points output ON Input signal voltage 24 VDC 10 Input signal current 7 mA...

Страница 41: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 42: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 43: ...C main unit refer to the Hardware Manual offered separately 24 24 S S B1 B0 3 3k FX 2N 1RM Class 3 grounding DC24V 10 15 The service power supply of the PC can be used within the allowable capacity 3...

Страница 44: ...ped and the output is turned off When the power is recovered the FX2N 1RM automatically restarts operation if the RUN PRG selector switch is set to RUN Cautions on wiring Do not connect the AC power s...

Страница 45: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 46: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 47: ...tput wiring transistor output type External power supply 5 to 30 VDC Circuit isolation Photocoupler isolation Maximum load Resistance load 0 5 A point 0 8 A 4 points common 1 6 A 8 points common Induc...

Страница 48: ...ns on wiring Do not connect the AC power supply to DC I O terminals or DC power terminals If such connection is performed the FX2N 1RM may burned out Do not perform wiring from the outside to an unuse...

Страница 49: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 50: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 51: ...r is supplied electrical shocks may occur Read thoroughly the manual and confirm safety before modifying a program during operation performing forced output performing the RUN operation or performing...

Страница 52: ...PRG mode when set to ON from OFF when the rising edge is detected b0 and b1 should not be set to ON from OFF at the same time Change in the status is detected in any procedure to change over the RUN m...

Страница 53: ...No to be executed using the method selected by the procedure described in Setting the bank specification method above bank specification Bank specification by the external input Specify an arbitrary p...

Страница 54: ...nd the angle advance quantity A to G for each step from the data setting panel or the PLC main unit The smallest rotation speed should be set in S0 with the settings increasing in sequential order of...

Страница 55: ...Rotation angle b FNC 15 BFM 15 Angle advance quantity B FNC 16 BFM 16 S2 Rotation angle c FNC 17 BFM 17 Angle advance quantity C FNC 18 BFM 18 S3 Rotation angle d FNC 19 BFM 19 Angle advance quantity...

Страница 56: ...peed 1degree 360 degrees revolution mode 415 r min 0 5 degrees 720 degrees revolution mode 207 r min The individual automatic angle advance function can be set in 7steps from S0 to S6 as shown in the...

Страница 57: ...vance quantity From the data setting panel Set by FNC 90 Refer to 8 3 6 Input by one time value From the PLC Input to BFM 6376 to 6459 Refer to the next page Input value equals advance angle 1 degree...

Страница 58: ...424 6427 6430 6433 6436 6419 6422 6425 6428 6431 6434 6437 6420 6423 6426 6429 6432 6435 6438 Y3 S0 S1 S2 S3 S4 S5 S6 6439 6442 6445 6448 6451 6454 6457 6440 6443 6446 6449 6452 6455 6458 6441 6444 64...

Страница 59: ...setting procedure using the data setting panel refer to Paragraph 8 2 10 Setting by the PLC The reference angle data is provided in BFM 1 The reference angle setting command is provided in BFM 3 b2 W...

Страница 60: ...indicates a numeric from 1 to 999 The writing of any data from the buffer memory to the EEPROM is prohibited Only the operations shown in the table below are allowed to be set on the data setting pane...

Страница 61: ...t the current angle transfer function by operating FNC7 Effective Refer to Paragraph 8 3 8 Setting by the PLC BFM 0 b3 is turned ON and the method of specifying the bank selects PLC BFM 0 b7 is turned...

Страница 62: ...e When input terminal B1 turns ON the power supply of FX2N 1RM while turned ON the data storage in BFM 106 is not executed When the terminal B1 is turned OFF once and the terminal B1 is turned ON agai...

Страница 63: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 64: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 65: ...o PLC W 3 8003 9003 1 Command 0 W 4 Output prohibition Y00 to Y17 0 Prohibits output when each bit is set to ON W 5 Output prohibition Y20 to Y37 0 Prohibits output when each bit is set to ON W 6 Outp...

Страница 66: ...00 step No 0 FFFF 1 value 1 degree 2 value 0 5 degree W K D1001 1002 ON angle of bank No 0 Y00 step No 1 FFFF 1 value 1 degree 2 value 0 5 degree W K D1002 1003 OFF angle of bank No 0 Y00 step No 1 FF...

Страница 67: ...0 to 9999 Third FX2N 1RM unit 2 BFM 100 to 105 has been included since version V2 00 from 1998 2 3 BFM 106 has been included since version V2 40 from 2002 1 All the buffer memories in the FX2N 1RM uni...

Страница 68: ...rom the PLC without fail when you use the current angle transfer function This function has been included since V2 40 Bit Description Initial value Remarks b0 Resolution 0 1 0 5 degree 720 degrees rot...

Страница 69: ...h bit of BFM 8003 9003 Bit Description Remarks b0 RUN Runs a program on rising edge Refer to Paragraph 7 1 b1 PRG Turns off output by PRG command received on rising edge Refer to Paragraph 7 1 b2 ADJ...

Страница 70: ...put prohibition 1 Prohibits output 0 Enables output b4 Y04 output prohibition 1 Prohibits output 0 Enables output b5 Y05 output prohibition 1 Prohibits output 0 Enables output b6 Y06 output prohibitio...

Страница 71: ...us 1 Y01 output ON operation 0 Y01 output OFF operation b3 Y03 output status 1 Y01 output ON operation 0 Y01 output OFF operation b4 Y04 output status 1 Y01 output ON operation 0 Y01 output OFF operat...

Страница 72: ...error is reset Functions in same way as ERROR LED b4 Writing in RUN mode Turned on while contents of program of bank currently executed are written to EEPROM Never modify program of same bank while th...

Страница 73: ...le can be indirectly read from a PLC main unit to two or more outputs of FX2N 1RM It is a function added from version V2 00 The BFM number which wants to be read to BFM 103 is written Then output on a...

Страница 74: ...contents of the BFM keep area are saved in the EEPROM 4 When the mode is changed over from PRG to RUN When a RUN command BFM 3 b0 is written from the PLC main unit to the FX2N 1RM on the rising edge...

Страница 75: ...n is given It is recommended to write the ON OFF angle data after one operation cycle from the initial pulse as shown in the program below All the buffer memories BFM of the FX2N 1RM accommodate 16 bi...

Страница 76: ...mple above the FX2N 1RM is changed over to the RUN mode by input to X000 of the PLC main unit and the FX2N 1RM is changed over to the PRG mode by input to X001 M8000 FROM K0 K10 K4Y0 K3 Outputs the ON...

Страница 77: ...to 57 octal number D300 to D315 ON OFF angle input M10 Writing instruction M11 Reading instruction Step 0 Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 ON angle D300 D302 D304 D306 D308 D310 D312...

Страница 78: ...number specification D1 0 to 57 Octal number decimal number place of 10 8 place of 1 Reading of turning on angle and turning off angle of specified step Change in step number data and reading address...

Страница 79: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 80: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 81: ...n of rotation direction Specifies rotation direction of resolver counterclockwise or clockwise PRG 8 13 Write protect of EEPROM Specifies availability of write to EEPROM prohibited or enabled PRG 8 14...

Страница 82: ...certain output No positive logic PRG 8 26 One phase pulse output 180 pulses rotation Outputs a pulse string from an arbitrary output No One phase 180 pulses rotation PRG 8 27 Two phase pulse output 90...

Страница 83: ...the CLR key 1 After having performed an erroneous operation or erroneous input the last operation can be undone by pressing the CLR key 2 The error indication can be cleared by pressing the CLR key Wh...

Страница 84: ...written to the EEPROM when the GO key is pressed Enter the OFF angle of the output Y00 Determine the OFF angle The ON OFF set angle of the output Y00 entered is written to the built in EEPROM BANK 0 O...

Страница 85: ...nd the ON OFF set angle of the output Y00 entered is written to the built in EEPROM CLR BANK 0 OUT 0 STEP 0 DEG 1 ON LED Lit OFF LED Exting uished Key operation Display 1 The ON angle of the output Y0...

Страница 86: ...EL flashes on the DEG DEL GO GO BANK 0 OUT 0 STEP 0 DEG Blank ON LED Lit OFF LED Exting uished Deleting the entire program BANK 0 OUT 0 STEP 0 DEG 1 ON LED Lit OFF LED Exting uished Key operation Disp...

Страница 87: ...Lit OFF LED Exting uished Key operation Display 1 The ON angle of the output Y00 already registered is displayed 0 DEL GO BANK GO STEP GO Specify the bank No 0 BANK 0 flashes OUT 0 flashes STEP 0 flas...

Страница 88: ...tion 2 The ON angle of the output Y00 of the copy destination bank is displayed The error indication E07 is displayed when the bank No specified as source is equivalent to the bank No specified as des...

Страница 89: ...ey is pressed while modification is performed the OFF angle of the same step is displayed When the ON OFF or GO key is pressed while data is newly written or when the ON OFF key is pressed while the e...

Страница 90: ...s on the DEG Start to set the ON angle of the output Y00 2 The current angle flashes 0 OUT GO Read the output Y00 0 STEP GO Read the step No 0 Rotate the resolver and stop it in a position in which it...

Страница 91: ...Key operation Display RUN RUN GO BANK 0 OUT Blank STEP Blank DEG 1 RUN LED Lit 1 The current value is displayed Example of current value display When the mode is changed over in the way RUN PRG RUN t...

Страница 92: ...splay to the previous status BANK 0 OUT 0 STEP 0 DEG ON LED Lit OFF LED 2 The ON angle of the output Y00 already registered is displayed flashes 1 Exting uished Exting uished 2 BANK b OUT Ad STEP Blan...

Страница 93: ...Key operation Display 1 Initial value resolution 1 degree 0 ON OFF BANK 0 OUT 0 STEP 0 DEG F00 ON LED Flashes OFF LED Exting uished When setting is finished the contents of the next FNC No FNC1 are di...

Страница 94: ...hed the contents of the next FNC No FNC3 are displayed GO FNC GO While the OFF LED is lit Write enabled While the ON LED is lit Write prohibited Power ON PRG mode BANK 0 OUT 0 STEP 0 DEG F03 ON LED Ex...

Страница 95: ...setting is finished the contents of the FNC5 are displayed While the OFF LED is lit Invalid While the ON LED is lit Valid Confirm the setting by referring to the ON OFF LED status BANK S OUT Pd STEP 0...

Страница 96: ...When setting is finished the contents of the next FNC No FNC15 are displayed 4 ON OFF 3 decimal point indicates 0 5 degree BANK S OUT Pd STEP 1 1 DEG 0 is displayed 2 Key operation Display 1 It indic...

Страница 97: ...ing the rotational speed and angle advance quantity by the undermentioned operation Power ON PRG mode BANK 0 OUT 0 STEP 0 DEG F05 Key operation Display 1 Initial value invalid 5 FNC The specification...

Страница 98: ...pushed and setting is possible When the GO key is pushed the ON angle advance quantity setting of S0 is displayed BANK d OUT EC STEP 0 DEG 0 Lit 2 ON LED Lit 2 ON angle advance quantity existing set...

Страница 99: ...e GO key is pushed the OFF angle advance quantity setting of S0 is displayed BANK d OUT EC STEP 0 DEG 0 Lit 3 ON LED Exting uished OFF LED Lit 3 OFF angle advance quantity existing set BANK d OUT EC S...

Страница 100: ...K d OUT EC STEP 0 DEG 50 flashes ON LED Exting uished OFF LED Lit ON OFF OFF angle advance quantity setting of S0 MAX 180 degrees Refer to paragraph 6 4 GO 5 From previous page 5 0 The rotational spee...

Страница 101: ...P 0 DEG F06 Key operation Display 1 Initial value Permission 6 FNC Prohibition of RUN to PRG operathion FNC6 GO GO ON OFF ON LED Exting uished OFF LED Lit 1 BANK 0 OUT 0 STEP 0 DEG F06 ON LED Flashes...

Страница 102: ...t set in a program cannot be inverted The error code E03 is displayed Power ON PRG mode BANK 0 OUT 0 STEP 0 DEG 1 ON LED Lit OFF LED Exting uished Key operation Display 1 The angle of the output Y00 a...

Страница 103: ...flashes on the DEG GO Batch addition FNC60 Specify the output No to be shifted Enter the angle to be added BANK 0 OUT 0 STEP 0 DEG 2 ON LED Lit OFF LED Exting uished 2 When setting is finished flashi...

Страница 104: ...ng uished GO BANK 2 0 GO OUT 6 2 FNC GO 123 flashes on the DEG GO Batch addition FNC62 Specify the output No to be shifted Enter the angle to be added BANK 0 OUT 0 STEP 0 DEG 2 ON LED Lit OFF LED Exti...

Страница 105: ...ting uished GO BANK 2 0 GO OUT 123 flashes on the DEG GO Batch addition FNC64 Specify the output No to be shifted Enter the angle to be added BANK 0 OUT 0 STEP 0 DEG 2 ON LED Exting uished OFF LED Lit...

Страница 106: ...s increment 1 ms BANK 0 OUT 13 STEP 0 DEG 1 ON LED Lit OFF LED Exting uished 1 When setting is finished flashing of data on the DEG is changed into display of the ON output set angle of Y13 GO T T T S...

Страница 107: ...from which a pulse string is to be output BANK 0 OUT 1 STEP 0 DEG 2 ON LED Lit OFF LED Exting uished 2 The ON angle of the output Y01 already registered is displayed GO Y0 0 OUT GO BANK 0 OUT 0 STEP...

Страница 108: ...already registered is displayed 0 BANK GO Specify an output No from which RUN output is to be performed BANK 0 OUT 1 STEP 0 DEG 2 ON LED Lit OFF LED Exting uished 2 The ON angle of the output Y01 alr...

Страница 109: ...BCD current value already registered is displayed 0 BANK Displaying the existing setting FNC70 to FNC75 Specify an output No from which the current value is to be output BANK 0 OUT 0 STEP 1 DEG Blank...

Страница 110: ...FNC80 Enter a keyword Set range 001 to 999 GO 2 1 3 BANK 0 OUT 0 STEP 0 DEG 2 GO 2 The ON angle of the output Y00 already registered is displayed FNC 123 flashes on the DEG ON LED Lit OFF LED Exting u...

Страница 111: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 112: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 113: ...creen displayed just before the mode was changed over from RUN to PRG is displayed Power ON PRG mode BANK Executed bank No OUT Blank STEP Blank DEG Current value RUN Lit Press the ON OFF key to change...

Страница 114: ...Monitor 9 9 2 FX2N 1RM E SET Programmable Cam Switch Memo...

Страница 115: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 116: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 117: ...STEP Displays 0 DEG Displays the existing set value ON LED Lit RUN LED Lit BANK Changing over to the test mode GO Press these keys at the same time After executing a bank whose data is to be modified...

Страница 118: ...nd the value is changed Modifying the ON angle and the OFF angle consecutively ON OFF While the ON LED is lit The ON angle is modified The angle is increased by 0 5 degree every time the key is presse...

Страница 119: ...played Determine the rotation speed modified The set value is written to the EEPROM and the output is changed Key operation Display Modifying the angle advance quantity of the automatic angle advance...

Страница 120: ...0 DEG 2 ON LED Exting uished OFF LED Exting uished FNC 9 0 GO ON OFF GO To change the setting of the next item the operation is repeated from step 1 An item can be selected with key 1 rpm or 1 degree...

Страница 121: ...d is to overlap the previous or next set value during modification the or key is not accepted just before the value entered overlaps the previous or next set value When the set value of the rotation s...

Страница 122: ...n Display The display status returns to the status before the test mode is selected BANK Terminating the test mode CLR Press these keys at the same time BANK Executed bank No OUT Blank STEP Blank DEG...

Страница 123: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 124: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 125: ...is not accepted Enter a correct ON OFF angle E03 When the ON OFF output was inverted using FNC50 the ON OFF data of the corresponding output had not been set Data not created cannot be inverted E05 T...

Страница 126: ...ilable to reset an error 1 Press the CLR key on the data setting panel 2 Turn on the error reset BFM 28 b3 by giving a TO instruction from the PLC main unit 3 Turn off the power then turn it on again...

Страница 127: ...Switch 1 Introduction 2 Installation 3 Specifications 4 External Wiring 5 Extension Block Specifications and External Wiring 6 Basic Setting 7 BFM Assignment 8 Program Operating Procedures 9 Monitor...

Страница 128: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 129: ...337 1338 1339 1340 1341 1342 1343 1344 1345 1346 1347 1348 1349 1350 1351 Y26 1352 1353 1354 1355 1356 1357 1358 1359 1360 1361 1362 1363 1364 1365 1366 1367 Y27 1368 1369 1370 1371 1372 1373 1374 137...

Страница 130: ...2106 2107 2108 2109 2110 2111 2112 2113 2114 2115 2116 2117 2118 2119 Y26 2120 2121 2122 2123 2124 2125 2126 2127 2128 2129 2130 2131 2132 2133 2134 2135 Y27 2136 2137 2138 2139 2140 2141 2142 2143 21...

Страница 131: ...2874 2875 2876 2877 2878 2879 2880 2881 2882 2883 2884 2885 2886 2887 Y26 2888 2889 2890 2891 2892 2893 2894 2895 2896 2897 2898 2899 2900 2901 2902 2903 Y27 2904 2905 2906 2907 2908 2909 2910 2911 29...

Страница 132: ...3642 3643 3644 3645 3646 3647 3648 3649 3650 3651 3652 3653 3654 3655 Y26 3656 3657 3658 3659 3660 3661 3662 3663 3664 3665 3666 3667 3668 3669 3670 3671 Y27 3672 3673 3674 3675 3676 3677 3678 3679 36...

Страница 133: ...4410 4411 4412 4413 4414 4415 4416 4417 4418 4419 4420 4421 4422 4423 Y26 4424 4425 4426 4427 4428 4429 4430 4431 4432 4433 4434 4435 4436 4437 4438 4439 Y27 4440 4441 4442 4443 4444 4445 4446 4447 44...

Страница 134: ...5178 5179 5180 5181 5182 5183 5184 5185 5186 5187 5188 5189 5190 5191 Y26 5192 5193 5194 5195 5196 5197 5198 5199 5200 5201 5202 5203 5204 5205 5206 5207 Y27 5208 5209 5210 5211 5212 5213 5214 5215 52...

Страница 135: ...5946 5947 5948 5949 5950 5951 5952 5953 5954 5955 5956 5957 5958 5959 Y26 5960 5961 5962 5963 5964 5965 5966 5967 5968 5969 5970 5971 5972 5973 5974 5975 Y27 5976 5977 5978 5979 5980 5981 5982 5983 59...

Страница 136: ...6714 6715 6716 6717 6718 6719 6720 6721 6722 6723 6724 6725 6726 6727 Y26 6728 6729 6730 6731 6732 6733 6734 6735 6736 6737 6738 6739 6740 6741 6742 6743 Y27 6744 6745 6746 6747 6748 6749 6750 6751 67...

Страница 137: ...FF STEP2 ON STEP2 OFF STEP3 ON STEP3 OFF STEP4 ON STEP4 OFF STEP5 ON STEP5 OFF STEP6 ON STEP6 OFF STEP7 ON STEP7 OFF Y00 Y01 Y02 Y03 Y04 Y05 Y06 Y07 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 Y20 Y21 Y22 Y23 Y24...

Страница 138: ...FX2N 1RM E SET Programmable Cam Switch Appendix A 10 Memo...

Страница 139: ...FX2N 1RM E SET Programmable Cam Switch...

Страница 140: ...OUCHI TOKYO 100 8310 HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN USER S MANUAL FX2N 1RM E SET PROGRAMMABLE CAM SWITCH Effective Apr 2003 Specification are subject to change without notice JY992D71101F M...