5 PROGRAMMING
The program enclosed by the dotted line is necessary only when the initial settings are changed.
Initial setting change
Error reset
Changing of initial settings
Processing at initial settings
Processing at error occurrence
Write of remote output signals
Initial settings
HOLD/CLEAR setting
(RWwB)
Turns on initial data
processing completion flag
(RY18).
Turns on initial data
setting request flag (RY19).
Turns on initial data setting
request flag (RY19).
Turns off initial data
processing completion flag
(RY18).
Turns off initial data setting
request flag (RY19).
Analog output enable/
disable setting (RWw8)
CH.1 to CH.4 output range
setting (RWw9)
Analog output enable/
disable setting (RWw8)
CH.1 to CH.4 output range
setting (RWw9)
Writes to master station
Writes to master station
Writes to master station
Turns on error reset
request flag (RY1A).
Turns off error reset
request flag (RY1A).
CH.1 digital value
setting (RWw0) : 500
CH.2 digital value
setting (RWw1) : 1000
Turns on CH.1 analog
output enable/disable
flag (RY00).
Turns on CH.2 analog
output enable/disable
flag (RY01).
Read CH. check code
(RWr0, RWr1).
Reads error code (RWr8).
Writes to master station
Y400 to Y41F are written
into RY00 to RY1F.
Analog output enable/disable specification
Setting of digital values
Digital value
setting
Analog output
enable