3 SPECIFICATION
3.5.2 Functions of the remote I/O signals
Table 3.6 explains the functions of the remote I/O signals of the AJ65VBTCU-68DAVN.
Table 3.7 Remote I/O Signal Details (1/2)
Device No.
Signal Name
Description
RXnC
E
2
PROM write error flag
Turns on the number of E
2
PROM write times exceeds its limit (1000,000 times per
channel). If this flag has turned on, this module itself has failed (hardware fault) and
therefore this flag cannot be reset (turned off) by the error reset request flag.
At occurrence of this error, power on the AJ65VBTCU-68DAVN again. If this flag turns
on after the power is switched on again, it is a hardware fault. Contact your nearest
Mitsubishi representative.
RX (n+1) 8
Initial data processing request
flag
After power-on, the initial data processing request flag is turned on by the AJ65VBTCU-
68DAVN to request the initial data to be set.
Also, after the initial data processing is complete (initial data processing complete flag
RY (n+1) 8 ON), the flag is turned off.
RX(n+1)8
Initial data processing request flag
RY(n+1)8
Initial data processing complete flag
RX(n+1)9
Initial data setting complete flag
RY(n+1)9
Initial data setting request flag
RX(n+1)B
Remote ready
: Performed by sequence ladder
: Performed by AJ65VBTCU-68DAVN
RX (n+1) 9
Initial data setting complete flag
When the initial data setting request (RY (n+1) 9 ON) is made, the flag turns on after
the initial data setting completion is done.
Also, after the initial data setting is complete, the initial setting complete flag turns off
when the initial data setting request flag turns off.
RX (n+1) A Error status flag
Turns on at occurrence of the output range setting error, digital value setting error or
E
2
PROM write error (RXnC).
Does not turn on at occurrence of the watchdog timer error.
(The "RUN" LED goes off.)
RX(n+1)A
Error status flag
RY(n+1)A
Error reset request flag
RWrn+8
Error code
RWrn to RWrn+7
CH. check code
: Performed by sequence ladder
: Performed by AJ65VBTCU-68DAVN
Error code
Check code
0
0
0
0
RX (n+1) B Remote READY
Turns on when initial data setting is completed after power-on or at termination of the
test mode.
(Used for interlocking read/write from/to the master module.)
n: Address allocated to the master module by station number setting.