5 - 2 5 - 2
MELSEC-A
5 PROGRAMMING
5.2 When Remote Net Ver. 1 Mode Is Used
5.2.1 Conditions of Program Example
The program examples in this section are created under the following conditions.
(1) System
configuration
PLC CPU
Master station
(X0 to X1F/Y0 to Y1F)
I/O (Output 64 points)
(Y60 to Y9F)
AJ65VBTCU-68DAVN
(Station number 1)
I/O (Input 64 points)
(X20 to X5F)
(2) Relationships between PLC CPU, master module and
AJ65VBTCU-68DAVN
AJ65VBTCU-68DAVN
(Station number 1)
PLC CPU
Device X
X400 to X40F
X410 to X41F
Device Y
Y400 to Y40F
Y410 to Y41F
Device D
D200
D201
D202
D203
Device D
D300
D301
D302
D303
Master module
Address
Remote input (RX)
RX00 to RX0F
RX10 to RX1F
E0
H
E1
H
Remote output (RY)
RY00 to RY0F
RY10 to RY1F
160
H
161
H
Remote register (RWw)
RWw0
RWw1
RWw2
RWw3
1E0
H
1E1
H
1E2
H
1E3
H
Remote register (RWr)
RWr0
RWr1
RWr2
RWr3
2E0
H
2E1
H
2E2
H
2E3
H
Remote input (RX)
RX00 to RX0F
RX10 to RX1F
Remote output (RY)
RY00 to RY0F
RY10 to RY1F
Remote register (RWw)
Remote register(RWr)
RWr0 CH.1 check code
D204
D205
D206
D207
RWw4
RWw5
RWw6
RWw7
1E4
H
1E5
H
1E6
H
1E7
H
D208
D209
D210
D211
RWw8
RWw9
RWwA
RWwB
1E8
H
1E9
H
1EA
H
1EB
H
D304
D305
D306
D307
RWr4
RWr5
RWr6
RWr7
2E4
H
2E5
H
2E6
H
2E7
H
D308
RWr8
RWr9
RWrA
RWrB
2E8
H
2E9
H
2EA
H
2EB
H
RWr8 Error code
RWrA Reserved
RWrB Reserved
RWr9 Reserved
RWr1 CH.2 check code
RWr2 CH.3 check code
RWr3 CH.4 check code
RWr4 CH.5 check code
RWr5 CH.6 check code
RWr6 CH.7 check code
RWr7 CH.8 check code
D309
D310
D311
In the program example (refer to Section 5.2.4) that uses the RRPA instruction (automatic refresh
parameter setting) with the ACPU/QCPU (A mode), RWr0 to RWr8 are assigned to D456 to D464.
RWw8 Analog output
enable/disable setting
RWw9 CH.1 to CH.4 output range
setting
RWwA CH.5 to CH.8 output range
setting
RWw0 CH.1 digital value setting
RWw1 CH.2 digital value setting
RWw2 CH.3 digital value setting
RWw3 CH.4 digital value setting
RWw4 CH.5 digital value setting
RWw5 CH.6 digital value setting
RWw6 CH.7 digital value setting
RWw7 CH.8 digital value setting
RWwB HOLD/CLEAR setting
5