111
Table 6.3 Error Code List for A2ASCPU(S1/S30) and A2USHCPU-S1 (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
"CHK
FORMAT
ERR"
(Checked at
STOP/
PAUSE
RUN.)
14
141
STOP
Instructions (including
) other than
,
,
and
are
included in the
instruction circuit block.
Check the program
of the
instruction and
correct it referring
to contents of
detailed error
codes.
142
Multiple
instructions
are given.
143
The number of contact
points in the
instruction circuit block
exceeds 150.
144
The
instructions
are not paired with the
instructions,
or 2 or more pairs of them
are given.
145
Format of the block shown
below, which is provided
before the
instruction
circuit block, is not as
specified.
146
Device number of D1 in
the
instruction is
different from that of the
contact point before the
instruction.
147
Index qualification is used
in the check pattern
circuit.
NOP
LDX
LDIX
ANDX
ANIX
CHK
CHK
CHK
CHK
LEDA CHK
LEDA CHKEND
CHK
CJ P
P254
CHK D1 D2
CJ P
Содержание MELSEC-A A1SCPUC24-R2