49
(11) Memory write protect Dip switch
Memory Write
Protect Range
(kbytes)
Setting Switch
A2SHCPU
A2ASCPU
A2SHCPU-S1
A2ASCPU-S1/S30
A2USHCPU-S1
0 to 16
1: ON
1: ON
16 to 32
2: ON
2: ON
48 to 64
4: ON
4: ON
64 to 80
Unused
5: ON
80 to 96
Unused
6: ON
96 to 112
Unused
7: ON
112 to 144
Unused
8: ON
144 to 256
Unused
9: ON
Latch clear method
1)
Turn the RUN/STOP key switch from the "STOP" position to the "L.CLR"
position several times to make the "RUN" LED start flashing.
2)
Turn the RUN/STOP switch from the "STOP" position to the "L.CLR"
position once more.
3)
The latch clear operation is completed when the "RUN" LED goes OFF.