![Mitsubishi FR - S500 Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/mitsubishi/fr-s500/fr-s500_instruction-manual_1809246018.webp)
8
Main circuit terminals
1.2.2
Cables, wiring length, and crimping terminals
The following table indicates a selection example for the wiring length of 20m (65.62
feet).
1) Three-phase 200V power input
2) Three-phase 400V power input
3) Single-phase 100V power input
Wiring length
100m (328.08 feet) maximum. (50m (164.04 feet) maximum for the FR-S540E-
0.4K-NA.)
Applied Inverter
Ter-
minal
Screw
size
Tight-
ening
Torque
N
⋅
m
Crimping
Terminal
Cable
PVC Insulation
Cable
mm
2
AWG
mm
2
R, S, T U, V, W R, S, T U, V, W R, S, T U, V, W R, S, T U, V, W
FR-S520E-0.1K
to 0.75K-NA
M3.5
1.2
2-3.5
2-3.5
2
2
14
14
2.5
2.5
FR-S520E-
1.5K, 2.2K-NA
M4
1.5
2-4
2-4
2
2
14
14
2.5
2.5
FR-S520E-
3.7K-NA
M4
1.5
5.5-4
5.5-4
3.5
3.5
12
12
4
2.5
Applied Inverter
Ter-
minal
Screw
size
Tight-
ening
Torque
N
⋅
m
Crimping
Terminal
Cable
PVC Insulation
Cable
mm
2
AWG
mm
2
R, S, T U, V, W R, S, T U, V, W R, S, T U, V, W R, S, T U, V, W
FR-S540E-
0.4K
to 3.7K-NA
M4
1.5
2-4
2-4
2
2
14
14
2.5
2.5
Applied Inverter
Termi-
nal
Screw
size
Tight-
ening
Torque
N
⋅
m
Crimping
Terminal
Cable
PVC Insulation
Cable
mm
2
AWG
mm
2
R, S U, V, W R, S U, V, W R, S U, V, W R, S
U, V, W
FR-S510WE-
0.1K
to 0.4K-NA
M3.5
1.2
2-3.5 2-3.5
2
2
14
14
2.5
2.5
FR-S510WE-0.75K-
NA
M4
1.5
5.5-4
2-4
3.5
2
12
14
4
2.5
CAUTION
•
When the wiring length of the 0.1K and 0.2K of the three-phase 200V and
single-phase 100V class and the 0.4K and 0.75K of the three-phase 400V class
is 30m (98.43 feet) or more, set the carrier frequency to 1kHz.
•
When automatic torque boost is selected in Pr. 98 "automatic torque boost
selection (motor capacity)", the wiring length should be 30m (98.43 feet)
maximum. (Refer to page 121.)
Содержание FR - S500
Страница 56: ...46 MEMO ...
Страница 164: ...154 MEMO ...
Страница 188: ...178 MEMO ...