57
DETAILS OF INPUT AND
OUTPUT SIGNALS
7
*3
Torque command can be set for the FR-A700 series only.
*4
When
Pr.544
= "100", RXC to RXF are remotely input available with the PLC function. (FR-A700 series NA/EC
version only)
For details, refer to the FR-A700 PLC function programming manual.
RXD
Frequency setting completion/torque
command setting completion
(RAM)
Switched on when the set frequency/torque is written to the
inverter RAM by the frequency/torque setting command (RYD)
switching on. Frequency/torque setting completion (RXD) is
switched off when the frequency/torque setting command (RYD) is
switched off.
RXE
Frequency setting completion/torque
command setting completion
(RAM, EEPROM)
Switched on when the set frequency/torque is written to the
inverter RAM and EEPROM by the frequency/torque setting
command (RYE) switching on. Frequency/torque setting
completion (RXE) is switched off when the frequency/torque
setting command (RYE) is switched off.
RXF
Instruction code execution completion
Switched on on completion of the processing corresponding to the
instruction code (RWw2,10,12,14,16,18) which is executed when the
instruction code execution request (RYF) switches on. Switched off
when the instruction code execution completion (RXF) is switched off.
RX1A
Error status flag
Switched on when an inverter error occurs (protective function is
activated).
RX1B
Remote station ready
Switched on when the inverter goes into the ready status on
completion of initial setting after power-on or hardware reset.
(Used as an interlock for read/write from/to the master unit.)
Switched off when an inverter error occurs (protective function is
activated).
Device
No.
Signal
Description