196
FDTN-H
Model FDTN308HEN
Operation data
(3)
Item
Model
FDTN308H
FDC306HEN3
Nominal cooling capacity
(1)
W
7100
Nominal heating capacity
(1)
W
7300
Power source
1 Phase, 220/240V, 50Hz
Cooling input
kW
3.07/3.11
Running current (Cooling)
A
15.6/16.3
Power factor (Cooling)
%
89/79
Heating input
kW
2.82/2.86
Running current (Heating)
A
14.5/15.2
Power factor (Heating)
%
88/78
Inrush current (L.R.A)
A
89
Noise level
(4)
dB(A)
Hi 41 Lo:35
56
Exterior dimensions
mm
Unit 260
×
840
×
840
844
×
950
×
340
Height
×
Width
×
Depth
Panel 30
×
950
×
950
Net weight
kg
30 (Unit:24 Panel:6)
69
Refrigerant equipment
–
RC5532ENE1
×
1
Compressor type & Q’ty
Motor
kW
–
2.24
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & bare tubing
Refrigerant control
Capillary tube
Capillary tube
Refrigerant
R22
Quantity
kg
Holding charged
1.3 [Pre-charged up to the piping length of 5m]
Refrigerant oil
r
–
1.63 (SUNISO 3GS)
Defrost control
IC controlled de-icer
High pressure control
High pressure regulator valve
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Propeller fan
×
1
Motor
W
30
×
1
60
×
1
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
Hi:17 Lo:12
54
Fresh air intake
Available
–
Air filter, Q’ty
Long life filter
×
1(washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
40 (Crank case heater)
Operation control
Operation switch
Wireless remote control switch
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Wireless remote controller. Drain hose
Optional parts
Decorative Panel
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard. JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1, JIS B8616
FDTN308HEN
Internal protector for compressor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Содержание FDT208HEN-S