When the unit is installed at the particular location as shown below, corrosion or failure may be caused. Please consult
the dealer from which you purchased the air-conditioner.
a) The place where corrosive gas is generated (hot spring, etc.).
b) The place where wind containing salt blows (seaside area).
c) The place where enveloped by oil mist.
d) The place where there is a machine that radiates electromagnetic wave.
Request
¡
Restrict the height of obstruction wall in front of the discharge air port to the height of unit or less.
¡
Do not enclose around the unit by the obstruction. Secure the top space for 1 m or more.
¡
When installing the units side by side in series, secure a space of 10 mm between units.
¡
When installing the unit where there is a concern about the short circuit, attach the guide louver in front of
discharge air port to prevent the short circuit.
¡
When installing plural units in a group, secure sufficient intake space to prevent the short circuit.
¡
When installing the unit where it is covered by snow, provide appropriate snow break means.
¡
When installing the unit where it is subject to strong wind, execute wind-breaking work.
(c)
The minimum space for installation
Select the space considering the direction of refrigerant piping.
Secure with the anchor bolt.
2)
Install the unit directing the
discharge air port at a right
angle to the wind direction.
(d) Location where strong wind blows against the unit
3)
Where the foundation is not
stable, secure the unit with
wire, etc.
Wind
direction
1)
Install the unit directing the
discharge air port to the wall.
500 or more
Wind
direction
Air
inlet
Air outlet
(Service space)
(2)
Carry-in and installation of unit
Pay sufficient attention to the carry-in and moving work of the unit, and always execute work by two persons or more.
(a)
Carry-in
1)
When carrying-in the unit, carry it in as packed condition to the installation site
as near as possible.
2)
If you are compelled to carry-in the unit unpacked condition, lift the unit by the
rope using a nylon sling or applying protection plates so that the unit is not
marred.
CAUTION
¡
Rope the unit taking the discrepancy of center of gravity into consideration.
Protection plate
Wood base
Air inlet
Open
space
Open
space
Open
space
Distance
Installation
example
FDC208, 258
1
FDC308
FDC408, 508
Unit : mm
L
1
L
2
L
3
L
4
300
100
5
2
5
150
5
3
500
100
5
Open
space
Open
space
Open
space
1
300
100
5
2
5
150
5
3
500
100
5
Open
space
Open
space
Open
space
1
300
150
5
2
5
300
5
3
500
150
5