- 22 -
b) The control box cover consists of two parts (top and bottom parts). Each can be removed separately
by unscrewing two screws and pulling the cover down. Connectors and dipswitches on the main board
can be operated by removing only the top part. Only remove the bottom part when servicing power
supply lines and transmission lines.
a) Remove the service panel by unscrewing the 6 screws as shown in the picture on the right.
(2) Control Box and Location of Terminals
1
Outdoor Unit
Front Panel
2
2
Restrictions on Transmission Lines
[1] Electrical Wiring
(1) Attention
1
Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations, and guidance of each electric power company.
2
Wiring for control (hereinafter referred to as transmission line) shall be (5cm or more) apart from power
source wiring so that it is not influenced by electric noise from power source wiring.(Do not insert trans-
mission line and power source wire in the same conduit.)
4
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is
sometimes removed at the time of service work.
5
Never connect 380~415V(220~240V )power source to terminal block of transmission line.If
connected,electrical parts will be burnt out
6
Use 2-core shield cable for transmission line. If transmission lines of different systems are wired with the
same multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations.
NO
OK
TB3
TB7
TB3
TB7
TB3
TB7
TB3
TB7
Multiple-core Cable
2-core Cable
2-core Cable
Indoor Unit
Indoor Unit
Outdoor Unit
Outdoor Unit