- 97 -
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
MA Remote controller
cannot be operated
Nothing appears
on the display
Units grouped by
MA remote controller?
LED2 on the controller
board of another
indoor unit is off
Power OFF on
all indoor units?
Does LED2 on the control
board in one of the indoor units
come on when MA remote
control line was disconnected?
Is there any indoor unit
whose LED2 on all
control boards are off?
Is the above condition
restored when rewired?
Check loosened screws
on remote control wiring
Go to P95 items 1-2
Check remote
controller wiring
Is indoor unit
powered off?
Short-circuited
remote controller
line?
Replace the indoor
unit controller board
LED1 on control board
in indoor unit blinking
(at 20 sec. intervals)
'HO' is displayed on
the screen and cannot
be turned off
Can the remote
controller be
operated?
Normal
(including the display
'Centralized Control')
Go to the section
on the error message
displayed
Check M-NET
transmission line
Go to P95 item 2
No2 Refrigerant
Circuit check
Is error message
6602 or 6607 displayed if
continuing to operate the
remote controller?
No.1-refrigerant
circuit is normal. No.2-
refrigerant circuit
would not start
Did you only turn
indoor units back on?
Go to P95 item 2
No.1-refrigerant
circuit check
Continues for 3
minutes or longer
Go to item 3 on P96
No (steady ON
or OFF)
Go to P95 item 1
Turn on the power
Turn on the power
Check wiring
Go to P95 item 1
When main power is turned on,
MA remote displays 'HO' while
the unit is starting up
Comes off within
3 minutes
Replace MA remote
controller
✻
After correcting the
problem, connect
back MA remote
controller line
Flow chart: When MA remote controller does not respond.