- 98 -
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Cannot be remote-controlled
DIPSW3-8
OFF?
DIPSW1-10
ON?
Is the dipswitch
'Normal/Maintenance' set
to 'Maintenance'?
Does the pulse
input conform to specified
value (over 200ms)?
Is indoor unit
malfunctioning?
Disconnect external wiring and
shot-circuit TB22 and BC-B1.
Apply voltage to AC-A1.
Short-circuit CN51-1 and -2
on the controller board.
Can unit be turned on and off?
Replace the controller board
Set DIPSW3-8 to ON.
Set DIPSW1-10 to OFF.
Set it to Normal.
Follow the specification (over 200ms).
Go to the section on the displayed error.
Check external wiring, or external pulse wave patterns.
Either input/output board or wiring between controller board
and input/output board needs to be replaced.
over 200ms
Under 200ms