System Using MA Remote Controller
(2) Unit with One Indoor Unit (20HP Systems)
Remarks
Maximum Allowable Length
Control Wiring Diagram
1. Use sequential numbers to set indoor unit address.
2. Do not connect TB5s' of the indoor units that are
connected to different outdoor units with each other.
3. Replace CN41 with CN40 on only one outdoor unit.
4. Ground only one of the outdoor units' S terminal of
TB7 (centralized control transmission terminal).
5. The outdoor unit cannot be connected to indoor units
other than the PFD-type ones.
<a. Indoor/Outdoor transmission line>
Maximum Length (above 1.25mm
2
)
L1, L2 200m
<b. Transmission line for centralized control>
Maximum length via outdoor unit (over 1.25mm
2
)
L1 + L3 + L2 500m
NO
NO
OC
TB3
TB7
E
A B
A B S
51
IC
MA
TB5-1
A B S
01
TB5-2
A B S
TB15
1
2
A1 B2
02
OC
TB3
TB7
E
A B
A B S
52
L31
L1
L2
Use CN41 as is.
✻
There are 2 indoor controller
boards inside indoor unit.
Replace CN41 with CN40.