(2) Outdoor Unit (Cooling Mode)
ations
Start
Breaker trip
Operation
mode
Error mode
Operation
mode
52C ON
Cooling operation
Refer to 2-(1) and 2-(3)
Go to indoor unit operation mode command
1
Error stop
Outdoor unit error display
on the LED
Self-holding of protection
function
Error message sent to
indoor units
2
Note 1
Cooling
Note 2
Note 3
Operation
command
Normal oper
Abnormal operations
At stoppage
From indoor unit
YES
YES
YES
YES
NO
NO
System
startup completed
(Approx.
1 minute)
NO
NO
1. 52C OFF
2. Inverter output 0Hz
3. Fan stop
4. All solenoid valves OFF
1. Self-holding of protection
function released
2. SLEV, LEV1 fully open
(outdoor unit)
Note 1: Searches for indoor unit remote control address information and group information for one minute
after power on.
Note 2: There could be problems with either indoor units or outdoor units. In either case, the corresponding
outdoor units or indoor units will make an error stop. (While running an emergency operation mode,
these units will remain in operation.)
Note 3: The operation mode is determined by the indoor unit.