–99–
1
B
A
Cooling
Heating
Stopped
Defrosting
SVA
ON
OFF
OFF
OFF
SVB
OFF
ON
OFF
OFF
SVC
ON
OFF
OFF
OFF
Mode
Branch port
Normal
Malfunction
CNTR(1)-(3)
Approximately 90
Ω
Open or shorted
CN03(1)-(3)
Approximately 1.7
Ω
* Disconnect the connector before measurering.
CNTR
CN03
BC Controller control board
Red
Blue
Brown
Brown
4) BC controller transformer
Solenoid valves (SVA, SVB, SVC, SVM1)
Coordination signals output from the board and solenoid valve operations. *Depending on the models, SVM is not built in.
Note 1 : (SVA, SVB, SVC)
SVA, SVB and SVC are turned on and off in accordance with operation mode.
(SVM1)
SVM is turned on and off in accordance with operation mode.
Note 2 : (SVA, SVB, SVC)
(SVM1)
Measure temperature of piping on either side of SVA
1
-
A
Measure temperature at points marked with an “X”.
Measure temperature of piping on either side of SVB
1
-
B
Operation Mode
Cooling-only
Cooling-principal
Heating-only Heating-principal
Defrosting
Stopped
SVM1
ON
OFF
OFF
OFF
ON
OFF
Содержание City Multi P500YEM-A
Страница 14: ...13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board...
Страница 15: ...14 Y C board SNB board...
Страница 16: ...15 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5...
Страница 17: ...16 RELAY 10 board RELAY 4 board...
Страница 70: ...69 1 3 2 4 CV5b CV7b SV7 SV8 Solenoid Valves Block 2 CV4b CV6b CV2b ST1 BV1 BV2 CV3b 1 2 3 4...
Страница 72: ...71 Check Valves Block2 1 3 5 7 6 4 2 CV5b CV4b CV6b CV2b ST1 BV1 BV2 CV3b Check Valves Block2 1 3 7 2 4 5 6...