–65–
Note: 1 If there are any units that are not operating, it will cause refrigerant to accumulate, so by all means operate all the
indoor units. Also, in order to prevent stable operation from being disrupted by the thermostat going OFF, set the trial
operation mode.
Note: 2 If the high pressure is stabilized, it is safe to judge that the operation condition is stable.
Judge that operation is stabilized or not stabilized by whether the compressor starts after 3 or more minutes have
passed.
Note: 3 When turning on SW1 to
1 2 3 4 5 6 7 8 9 10
ON
, the LED will display the liquid level.
Note: 4 If AL = 1, it indicates that adjustment is not necessary, but when the liquid level is on the low side even if it is in the
AL = 1 region, if one unit only is run and refrigerant is accumulating in the units that are stopped, it may result in
there being insufficient refrigerant, so at such a time, adjustment is necessary.
Note: 5 Determine the difference in the volume of refrigerant necessary for cooling and for heating as follows, and carry out
supplementary charging in accordance with the table below.
* The piping length is the total pipe length calculated for a high press pipe with a
ø
25.4 size.
If the liquid pipe size is
ø
12.7, the actual length is 0.3
If the liquid pipe size is
ø
9.52, the actual length is 0.2
If the liquid pipe size is
ø
6.35, the actual length is 0.1
Pipe Length
Additional Refrigerant
Volume
60 m or less
60 ~ 90 m
90 m or longer
18 kg
27 kg
31 kg
Содержание City Multi P500YEM-A
Страница 14: ...13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board...
Страница 15: ...14 Y C board SNB board...
Страница 16: ...15 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5...
Страница 17: ...16 RELAY 10 board RELAY 4 board...
Страница 70: ...69 1 3 2 4 CV5b CV7b SV7 SV8 Solenoid Valves Block 2 CV4b CV6b CV2b ST1 BV1 BV2 CV3b 1 2 3 4...
Страница 72: ...71 Check Valves Block2 1 3 5 7 6 4 2 CV5b CV4b CV6b CV2b ST1 BV1 BV2 CV3b Check Valves Block2 1 3 7 2 4 5 6...