–141–
8
PREPARATION, REPAIRS, AND REFRIGERANT REFILLING WHEN REPAIRING
LEAKS
[1] Location of leaks: Extension piping or indoor units (when cooling)
(Pump down operation)
1
Attach a pressure gauge to the low-pressure servicing check joint (CJ2).
2
Stop all of the indoor units. When the compressor has stopped, shut off the liquid ball valve (BV2) for the outdoor
unit.
3
Stop all of the indoor units. When the compressor has stopped, turn the SW3-6 switch on the main board for the
outdoor unit to ON. (This will start the pump down operation, causing all of the indoor units to enter the cooling
mode.)
4
While in the pump-down operation (SW3-6 ON), the low pressure (LPS) will reach below 0.20 MPa, or the indoor
unit and the compressor will automatically shut down within 15 minutes of starting the pump-down operation.
Shut down all of the indoor units and the compressor if the pressure gauge for the low-pressure servicing joint
(CJ2) reads 0.15 MPa or after running the pump down operation for 20 minutes.
5
Shut off the gas ball valve (BV1) for the outdoor unit.
6
Remove any refrigerant remaining in the extension piping and the indoor units.
Be sure to recover the refrigerant without releasing it into the air.
7
Repair the location of the leak.
8
After repairing the leak, create a vacuum to remove any air from inside of the extension piping or the indoor
units.
9
Open the ball valves for the outdoor unit (BV1 and BV2), turn the SW3-6 switch to OFF, adjust refrigerant levels,
and confirm proper circulation.
Содержание City Multi P500YEM-A
Страница 14: ...13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board...
Страница 15: ...14 Y C board SNB board...
Страница 16: ...15 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5...
Страница 17: ...16 RELAY 10 board RELAY 4 board...
Страница 70: ...69 1 3 2 4 CV5b CV7b SV7 SV8 Solenoid Valves Block 2 CV4b CV6b CV2b ST1 BV1 BV2 CV3b 1 2 3 4...
Страница 72: ...71 Check Valves Block2 1 3 5 7 6 4 2 CV5b CV4b CV6b CV2b ST1 BV1 BV2 CV3b Check Valves Block2 1 3 7 2 4 5 6...