–123–
Checking
code
6607
(continued)
Meaning, detecting method
System
compo-
sition
Generating
unit address
Display of
trouble
Detecting
method
Cause
Checking method & countermeasure
No ACK error
When no-ACK signal is detected 6 consecutive intervals of 30 seconds by transmission
side controller, the transmission side detects error.
Note:
The address/attribute shown on remote controller indicates that the
controller is not sending acknowledgement signals.
(3) Connecting system with system controller (MELANS)
1
Outdoor
unit (OC)
2
BC
controller
<master>
(BC)
3
BC
controller
<slave>
(BS)
4
Indoor
unit (IC)
5
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
System
controller
(SC)
Remote
controller
(RC)
System
controller
(SC)
No reply
(ACK) at OC
transmis-
sion to BC
No reply
(ACK) at
BC <master>
transmis-
sion to IC
No reply
(ACK) at
BC <slave>
transmission
to BC <master>
No reply
(ACK) at IC
transmis-
sion RC
No reply
(ACK) at IC
transmis-
sion to SC
No reply
(ACK) at RC
transmission
to IC
No reply
(ACK) at
RC
transmis-
sion to
MELANS
Same as that for single refrigerant system.
Same as that for single refrigerant system.
Same as that for single refrigerant system.
Same cause as that of grouping from plural re-
frigerants.
Problem with partial IC units:
1) Same cause as that for single refrigerant system.
Problem with all IC in one refrigerant system:
1) Cause of total capacity error.
(7100)
2) Cause of capacity code setting error. (7101)
3) Cause of connecting number error. (7102)
4) Cause of address setting error.
(7105)
5) Disconnection or short circuit of transmission line
of OC unit terminal block for central control (TB7).
6) Power source shut down of OC unit.
7) Trouble of OC unit electrical system.
Problem with all IC:
1) As same that for single refrigerant system.
2) Insertion of power supply connector (CN40) into
OC unit transmission line for centralized control.
3) Disconnection or power source shut down of
power supply unit for transmission line.
4) Faulty system controller (MELANS).
Same cause as that for plural refrigerant system.
Problem with partial IC units:
1) Same cause as that of single refrigerant system.
Problem with all IC in one refrigerant system:
1) Error detected by OC unit.
Total capacity error.
(7100)
Capacity code setting error. (7101)
Connecting number error.
(7102)
Address setting error.
(7105)
2) Disconnection or short circuit of transmission line
of OC unit terminal block for central control (TB7).
3) Power source shut down of OC unit.
4) Trouble of OC unit electrical system.
Problem with all IC:
1) As same that for single refrigerant system.
2) Insertion of power supply connector (CN40) into
OC unit transmission line for central-ized control.
3) Disconnection or power shutdown of power
supply unit for transmission line.
4) Faulty MELANS.
Same countermeasure as that for single
refrigerant system.
Same countermeasure as that for single
refrigerant system.
Same countermeasure as that for single
refrigerant system.
Same countermeasure as that for IC unit
error in plural refrigerant system.
→
Same countermeasure as that for
single refrigerant system.
Confirm OC trouble diagnosis LED.
→
During fault generation, check the
LED check codes.
Check the content of 5)~7) shown left.
Confirm voltage of transmission line for
centralized control.
• More than 20V
→
Confirm 1) 2) left.
• Less than 20V
→
Confirm 3) left.
Same countermeasure as that for plur-
al refrigerant system.
→
Same countermeasure as that for
single refrigerant system.
Confirm OC trouble diagnosis LED.
→
Upon encountering a problem, check
the content according to check code.
Check the content of 2)~4) shown on the
left.
Check the causes of 1) ~ 4) on the left.
Содержание City Multi P500YEM-A
Страница 14: ...13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board...
Страница 15: ...14 Y C board SNB board...
Страница 16: ...15 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 SW5...
Страница 17: ...16 RELAY 10 board RELAY 4 board...
Страница 70: ...69 1 3 2 4 CV5b CV7b SV7 SV8 Solenoid Valves Block 2 CV4b CV6b CV2b ST1 BV1 BV2 CV3b 1 2 3 4...
Страница 72: ...71 Check Valves Block2 1 3 5 7 6 4 2 CV5b CV4b CV6b CV2b ST1 BV1 BV2 CV3b Check Valves Block2 1 3 7 2 4 5 6...