4. FUNCTIONS
MELSEC-A
4-16
(b)
Error codes
The error codes are shown below.
Error
Data
Detailed data
Communi-
Code
length
1
2
3
cation state
0200h
(c)
Ref.
(c)
Ref.
(c)
Ref.
(c)
Ref.
(c) Ref.
(c) Ref.
1121h
1
03h
The slave address specified in the parameter is the
same as that of the master. This error occurs
immediately after the power supply is turned on or
the CPU is reset. Even though this error is
occurring, if the exchange start (Y00) is on then
error of error code 3000h will occur, the FAULT
LED will turn on, and operation will stop.
×
1300h
2
Contents
ref.
Contents
ref.
Not even 1 active slave station is set in the
parameter. When this error occurs the detailed
data is set to:
Detailed data 1: Number of slaves set in the
parameter.
Detailed data 2: Number of active slaves set in
the parameter.
This error occurs immediately after the power
supply is turned on or the CPU is reset. Even
though this error is occurring, if the exchange start
(Y00) is on then error of error code 3000h will
occur, the FAULT LED will turn on, and operation
will stop.
×
1) Set 1 or more active
slaves in the
parameter.
2) When the FAULT
LED is turned on,
reset is enabled by
turning OFF
→
ON
→
OFF the Y0D
3000h
1
Ignored
1) When the above errors 1300h or 1121h have
occurred before this error:
Refer to errors 1300h, 1121h above.
2) Otherwise
An unexpected error has occurred.
×
For 1)
Refer to the above
1300h, 1121h
errors.
For 2)
Contact the nearest
Mitsubishi Electric
branch office or
dealer.
×
: Exchange stops after the error occurs.
: Exchange continues.
User processing
Description