2. SYSTEM CONFIGURATION
MELSEC-A
2-5
2.6
Precautions for Configuring a System
(1) There are the following restrictions on the AJ71PB92D/A1SJ71PB92D according to the
applied CPU module and used configuration software.
Parameter File Write Path
Max. I/O Data Length
CPU
Module
Configuration
Software
Via
AJ71PB92D/
A1SJ71PB92D
RS-232C
interface
Via
CPU module
RS-232C/
RS-422
interface
Normal service
mode
Extended
service mode
SW0D5F-
PROFIMAP
32 bytes each for
input and output
MELSEC-
PROFIMAP 2.0
Q series
CPU
MELSEC-
PROFIMAP 3.0
244 bytes each
for input and
output*1
SW0D5F-
PROFIMAP
32 bytes each for
input and output
MELSEC-
PROFIMAP 2.0
Write disabled
A/QnA
series
CPU
MELSEC-
PROFIMAP 3.0
Write enabled
Write enabled*1
32 bytes each for
input and output
244 bytes each
for input and
output*1
*1: The software version usable by the AJ71PB92D/A1SJ71PB92D is AJ71PB92D (A or
later) or A1SJ71PB92D (E or later).
When A1SJ71PB92D (software version D or earlier) is used, write is disabled and the
max. data length is 32 bytes each for input and output.
(2) Precautions for using the parameters preset for extended service mode to operate the
module in normal service mode.
The following table gives the operating conditions (conditions per one slave station) for the time
when the parameters preset for the extended service mode are used to operate the
AJ71PB92D/A1SJ71PB92D preset for the normal service mode/extended service mode.
: Operable
5
: Inoperable
Parameter Size
Exchange Data Length
Operating Condition
AJ71PB92D
A1SJ71PB92D
122 bytes max
244 bytes max
32 bytes max
244 bytes max.
AJ71PB92D software version A
or later and normal service
mode setting
5
A1SJ71PB92D software version
E or later and normal service
mode setting
5
A1SJ71PB92D software version
D or earlier and extended
service mode setting
5
5
(3) In either of the following cases, the AJ71PB92D/A1SJ71PB92D buffer memory must be
accessed by a sequence program when the module ready signal X1D of the
AJ71PB92D/A1SJ71PB92D is ON.
•
The operation mode is changed using Y11/X11 in the sequence program.
•
Parameter setting is made with ProfiMap connected to other than the RS-232C port of
the AJ71PB92D/A1SJ71PB92D. (For example, parameter setting is made with ProfiMap
connected to the RS-422/RS-232 connector of the CPU module.)
If the buffer memory is accessed with the X1D status ignored, the CPU module may detect
the "SP UNIT DOWN" error, stopping the sequence operation.