Service
-
-
E35 - High HX temp
YES
YES
YES
NO
NO
NO
NO
YES
Are the characteristics of the heat
exchanger sensor (Tho-R1, R2)
OK?
Is the air circulation around the
outdoor unit done properly?
Is the high pressure protection control
activated properly?
Does the temperature (external
gauge) correspond with the
displayed temperature in the event
of an alarm?
Too much refrigerant.
Recharge correct amount of refrigerant.
Replace defective sensor.
- Is the air circulation at the outdoor
unit obstructed?
- Is the installation space sufficient?
- Is the heat exchanger clogged?
Check the operation data with
logging tool.
Defective control PCB - replace.
Troubleshooting guide
Содержание FDCW100VNX
Страница 7: ...For Home Owners 6 For Home Owners ...
Страница 20: ...Installation 19 Installation ...
Страница 42: ...Control 41 Control ...
Страница 66: ...System description 65 System description ...
Страница 81: ...Service 80 Service ...
Страница 138: ...Service Component replacement HM270V FDCW100VNX K E L LEK 1 2 5 6 LEK 3 4 LEK 7 LEK LEK LEK Component replacement ...
Страница 148: ...Components 147 Components ...
Страница 155: ...Technical data 154 Technical data ...
Страница 156: ...Technical data Electrical circuit diagram 155 Electrical circuit diagram HM270V ...
Страница 157: ...Technical data Electrical circuit diagram 156 ...
Страница 158: ...Technical data Electrical circuit diagram 157 ...
Страница 159: ...Technical data Electrical circuit diagram 158 ...
Страница 160: ...Technical data Electrical circuit diagram 159 ...
Страница 166: ...Technical data 165 Dimensions Indoor unit 32 32 55 95 65 52 185 40 42 645 30 60 1760 350 337 127 500 550 Dimensions ...