E45 - Inverter communication error
YES
YES
YES
YES
OK
NO
NO
NO
NO
Is the connection between the
control PCB and the inverter
PCB ok?
Are JSW10, 11 on the inverter
PCB all set to open?
Does the LED on the inverter PCB
flash?
Replace the control PCB.
Has the fault been corrected?
Correct the connection.
Set JSW10, 11 to open.
Check why the inverter PCB has
no power.
- Defective fan motor?
Replace the inverter PCB.
Troubleshooting guide