Service
-
-
YES
YES
YES
Connect it.
NO
NO
NO
NO
YES
Cont’d from
previous page
Are the service valves fully open?
Are the connections to the low
pressure sensor and sensor for
suction gas temperature OK?
Are the characteristics of the low
pressure sensor and sensor for
suction gas temperature OK?
Is the low pressure normal during
operation?
Defective control PCB - replace.
Top up refrigerant.
Defective low pressure sensor
or sensor for suction gas
temperature - replace.
Open the service valves.
Troubleshooting guide