- 3 -
z
We recommend you to read this “SAFETY PRECAUTIONS” carefully before the installation work in order to gain full
advantage of the functions of the unit and to avoid malfunction due to mishandling.
z
The precautions described below are divided into
and
. The matters with possibilities leading to
serious consequences such as death or serious personal injury due to erroneous handling are listed in the
and
the matters with possibilities leading to personal injury or damage of the unit due to erroneous handling including probability
leading to serious consequences in some cases are listed in
. These are very important precautions for safety.
Be sure to observe all of them without fail.
z
Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating
methods as well as the maintenance methods of this equipment to the user according to the owner's manual.
z
Keep the installation manual together with owner’s manual at a place where any user can read at any time. Moreover if
necessary, ask to hand them to a new user
When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation
(piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces
z
Installation must be carried out by the qualified installer.
If you install the system by yourself, it may cause serious trouble such as water leaks, electric shocks, fire and personal injury ,
as a result of a system malfunction.
z
Install the system in full accordance with the instruction manual.
Incorrect installation may cause bursts, personal injury, water leaks, electric shocks and fire.
z
Use the original accessories and the specified components for installation.
If parts other than those prescribed by us are used, It may cause water leaks, electric shocks, fire and personal injury.
z
When installing in small rooms, take prevention measures not to exceed the density limit of refrigerant inthe event of
leakage.
Consult the expert about prevention measures. If the density of refrigerant exceeds the limit in the event of leakage, lack of oxygen can
occur, which can cause serious accidents.
z
Ventilate the working area well in the event of refrigerant leakage during installation.
If the refrigerant comes into contact with naked flames, poisonous gas is produced.
z
After completed installation, check that no refrigerant leaks from the system.
If refrigerant leaks into the room and comes into contact with an oven or other hot surface, poisonous gas is produced.
z
Hang up the unit at the specified points with ropes which can support the weight in lifting for portage. And to avoid jolting
out of alignment, be sure to hang up the unit at 4-point support.
An improper manner of portage such as 3-point support can cause death or serious personal injury due to falling of the unit
z
Install the unit in a location with good support.
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
z
Ensure the unit is stable when installed, so that it can withstand earthquakes and strong winds.
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
z
Ensure that no air enters in the refrigerant circuit when the unit is installed and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit becomes too high, which can cause burst and personal
injury.
z
The electrical installation must be carried out by the qualified electrician in accordance with “the norm for electrical work”
and “national wiring regulation”, and the system must be connected to the dedicated circuit.
Power supply with insufficient capacity and incorrect function done by improper work can cause electric shocks and fire.
z
Be sure to shut off the power before starting electrical work.
Failure to shut off the power can cause electric shocks, unit failure or incorrect function of equipment.
z
Be sure to use the cables conformed to safety standard and cable ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production or fire.
z
Use the prescribed cables for electrical connection, tighten the cables securely in terminal block and relieve the cables
correctly to prevent overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat production or fire.
z
Arrange the wiring in the control box so that it cannot be pushed up further into the box. Install the service panel
correctly.
Incorrect installation may result in overheating and fire.
z
Do not perform brazing work in the airtight room.
It can cause lack of oxygen.
z
Use the prescribed pipes, flare nuts and tools for R410A.
Using existing parts (for R22 or R407C) can cause the unit failure and serious accidents due to burst of the refrigerant circuit.
z
Tighten the flare nut by using double spanners and torque wrench according to prescribed method. Be sure not to tighten
the flare nut too much.
Loose flare connection or damage on the flare part by tightening with excess torque can cause burst or refrigerant leaks which
may result in lack of oxygen.
WARNING
SAFETY PRECAUTIONS
Содержание FDCW100VNX
Страница 7: ...For Home Owners 6 For Home Owners ...
Страница 20: ...Installation 19 Installation ...
Страница 42: ...Control 41 Control ...
Страница 66: ...System description 65 System description ...
Страница 81: ...Service 80 Service ...
Страница 138: ...Service Component replacement HM270V FDCW100VNX K E L LEK 1 2 5 6 LEK 3 4 LEK 7 LEK LEK LEK Component replacement ...
Страница 148: ...Components 147 Components ...
Страница 155: ...Technical data 154 Technical data ...
Страница 156: ...Technical data Electrical circuit diagram 155 Electrical circuit diagram HM270V ...
Страница 157: ...Technical data Electrical circuit diagram 156 ...
Страница 158: ...Technical data Electrical circuit diagram 157 ...
Страница 159: ...Technical data Electrical circuit diagram 158 ...
Страница 160: ...Technical data Electrical circuit diagram 159 ...
Страница 166: ...Technical data 165 Dimensions Indoor unit 32 32 55 95 65 52 185 40 42 645 30 60 1760 350 337 127 500 550 Dimensions ...