Service
- 104 -
33
Description
Alarm text on the
display
Alarm
no.
May be due to
S. fault Liquid line
Sensor fault, liquid line (BT15).
- Open-circuit or short-circuit on sensor input
Also see the troubleshooting guide on page 116.
- Sensor does not work (see “Temperature sensor”
section)
FDCW100VNX alarm
Description
Alarm text on the
display
Alarm
no.
May be due to
E5
E35
E36
E37
E38
E39
OU Com. error
High HX temp
Permanent Hotgas
S. fault Tho-R
S. fault Tho-A
S. fault Tho-D
Communication between the outdoor unit and
HM270V is not made.
Temperature deviation on the hot gas sensor (Tho-
R1/R2) five times within 60 minutes or under 60
minutes.
- Isolator switch for FDCW100VNX off
- Electrical noise from the other equipment.
- Insufficient air circulation or blocked heat exchang-
er
- Blocked filter
- Open-circuit or short-circuit on sensor input
- Defective control PCB in FDCW100VNX
Also see the troubleshooting guide on page 119.
-Defective control PCB in FDCW100VNX
Also see the troubleshooting guide on page 118.
- If the fault persists during cooling, there may be an
insufficient amount of refrigerant.
- Sensor does not work (see “Temperature sensor”
section)
- Sensor does not work (see “Temperature sensor”
section)
- Open-circuit or short-circuit on sensor input
- Defective control PCB in FDCW100VNX
Also see the troubleshooting guide on page 120.
- Sensor does not work (see “Temperature sensor”
section)
- Open-circuit or short-circuit on sensor input
- Defective control PCB in FDCW100VNX
Also see the troubleshooting guide on page 121.
- Sensor does not work (see “Temperature sensor”
section)
- Sensor does not work (see “Temperature sensor”
section)
- Insufficient air circulation or blocked heat exchang-
er
- Defective control PCB in FDCW100VNX
- Too much refrigerant
Also see the troubleshooting guide on page 117.
Temperature deviation on the hot gas sensor (Tho-D)
two times within 60 minutes or under 60 minutes.
Sensor fault, heat exchanger in FDCW100VNX
(Tho-R).
Sensor fault, outdoor air sensor in FDCW100VNX
(Tho-A).
Sensor fault, hot gas in FDCW100VNX (Tho-D).
Alarm list
Содержание FDCW100VNX
Страница 7: ...For Home Owners 6 For Home Owners ...
Страница 20: ...Installation 19 Installation ...
Страница 42: ...Control 41 Control ...
Страница 66: ...System description 65 System description ...
Страница 81: ...Service 80 Service ...
Страница 138: ...Service Component replacement HM270V FDCW100VNX K E L LEK 1 2 5 6 LEK 3 4 LEK 7 LEK LEK LEK Component replacement ...
Страница 148: ...Components 147 Components ...
Страница 155: ...Technical data 154 Technical data ...
Страница 156: ...Technical data Electrical circuit diagram 155 Electrical circuit diagram HM270V ...
Страница 157: ...Technical data Electrical circuit diagram 156 ...
Страница 158: ...Technical data Electrical circuit diagram 157 ...
Страница 159: ...Technical data Electrical circuit diagram 158 ...
Страница 160: ...Technical data Electrical circuit diagram 159 ...
Страница 166: ...Technical data 165 Dimensions Indoor unit 32 32 55 95 65 52 185 40 42 645 30 60 1760 350 337 127 500 550 Dimensions ...