48
–
Code
No.
Write contents
Record data
Data write range
Unit of
write
Number
of bytes
Contents
<Protection control status>
68 Protection control
Status 1
1
Bit0 HP protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit1
HP protection 2 (
*1)
Indoor EEV minimal opening
control at heating stop
0: Normal, 1: Implementing
Bit2
HP protection 3
Indoor EEV Control at heating
overload
0: Normal, 1: Implementing
Bit3
HP protection 4
Indoor unit forced thermostat OFF
control under heating at overload
0: Normal, 1: Implementing
Bit4 LP protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit5
LP protection 2
Compressor speed increasing rate
control
0: Normal, 1: Implementing
Bit6
LP protection 3 (
*1)
Outdoor EEV control
0: Normal, 1: Implementing
Bit7 Td protection 1
Compressor capacity control
0: Normal, 1: Implementing
69 Protection control
Status 2
1
Bit0
Td protection 2 (
*1)
Compressor dilution ratio
protection control
0: Normal, 1: Implementing
Bit1
Td protection 3 (
*1)
Indoor EEV minimal opening
control at heating stop
0: Normal, 1: Implementing
Bit2
Td protection 4 (
*1)
Outdoor EEV control
0: Normal, 1: Implementing
Bit3 Compression ratio protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit4
Compression ratio protection 2 (
*1)
Outdoor EEV control
0: Normal, 1: Implementing
Bit5 CS protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit6 PT protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit7 (Spare) Tc protection 1
Compressor capacity control
0: Normal, 1: Implementing
70 Protection control
Status 3
1
Bit0
CS protection 2
Compressor frequency upper limit
control
0: Normal, 1: Implementing
Bit1 (Spare)
0: Normal, 1: Implementing
Bit2 (Spare)
0: Normal, 1: Implementing
Bit3 (Spare)
0: Normal, 1: Implementing
Bit4 (Spare)
0: Normal, 1: Implementing
Bit5 (Spare)
0: Normal, 1: Implementing
Bit6 (Spare)
0: Normal, 1: Implementing
Bit7 (Spare)
0: Normal, 1: Implementing
71 Cause of compressor stop
0 - 127
–
1
18 – 1. Operation information
'17 • KX-SM-272