108
–
E63
E63
Emergency stop
Keeps flashing
Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Indoor unit
Diagnosis
Countermeasure
Is the
remote control setting
of Emergency Stop
"Valid"?
Is ON
signal inputted to the
CnT terminal of indoor
control PCB?
Save data for 30 minutes before stopping in Mente PC.
YES
NO
NO
YES
Check and save the data of
operating condition.
Check if it occurred during
operation or at the power
on.
Replace indoor control
PCB.
Change the remote control
setting of Emergency Stop
"Invalid"
Check the cause of
emergency stop.
(It is better to have the
data for 30 minutes before
stopping, when discussing
with an installer.)
2. Error detection method
If ON signal inputted to the CnT
terminal of indoor control PCB.
3. Condition of error displayed
Same as above
4. Presumable cause
Occurrence of emergency stop
factor
Note:
Indoor unit detected emergency stop commands all stop.
Check whether wrong remote control setting of emergency stop was done or not.
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
'17 • KX-SM-272
Содержание 140KXZEN1
Страница 153: ... 17 KX SM 272 151 ...
Страница 154: ... 17 KX SM 272 152 ...
Страница 155: ... 17 KX SM 272 153 ...
Страница 156: ... 17 KX SM 272 154 ...
Страница 165: ... 163 MEMO 17 KX SM 272 ...