39
–
Code
No.
Contents of data display
Data display range Minimum
unit
Remarks
C56 Target Fk
0 - 999
1Hz
C57 Inverter 1 operation frequency command 0 - 130
1Hz
C58 (Spare) Inverter 2 operation frequency
command
0 - 130
1Hz
C59 FMo1 Fan Speed command
0 - 999
10min
-1
C60 (Spare) FMo2 Fan Speed command
0 - 999
10min
-1
<Control status>
C61 Control status
0,1
(0: Close, 1: Open)
–
Order of 100: Oil return control ON
Order of 10: Defrosting ON
Order of 1: (Spare)
C62 Control status
0,1
(0: Close, 1: Open)
–
Order of 100: Test run control ON
Order of 10: Demand control ON
Order of 1: Silent mode control ON
C63 Control status
0,1
(0: Close, 1: Open)
–
Order of 100: Capacity measurement mode ON
Order of 10: (Spare)
Order of 1: (Spare)
C64 (Spare)
0,1
(0: Close, 1: Open)
–
Order of 100:
Order of 10:
Order of 1:
C65 Protection control status
0,1
(0: Close, 1: Open)
–
Order of 100: HP control by compressor speed
down control ON
Order of 10: LP control by compressor
speed down control ON
Order of 1: Td control by compressor
speed down control ON
C66 Protection control status
0,1
(0: Close, 1: Open)
–
Order of 100: Compression ratio control by
compressor speed down control
ON
Order of 10: CS control by compressor
speed down control ON
Order of 1: PT control by compressor
speed down control ON
C67 (Spare)
0,1
(0: Close, 1: Open)
–
Order of 100: Tc control by compressor speed
down control ON
Order of 10: (Spare)
Order of 1: (Spare)
C68 Compressor stop cause
0 - 127
1
*1
C69 (Spare)
0,1
(0: Close, 1: Open)
–
Order of 100:
Order of 10:
Order of 1
'17 • KX-SM-272