background image

6

a

d

c

b

e

f

90

°

d

c

b

a

5. Refrigerant piping work

b

a

a

b

e

b

c

d

c

A

5.2. Flaring work

• Main cause of gas leakage is defect in flaring work.

Carry out correct flaring work in the following procedure.

5.2.1. Pipe cutting (Fig. 5-3)

• Using a pipe cutter cut the copper tube correctly.

5.2.2. Burrs removal (Fig. 5-4)

• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in

order to avoid burrs drop in the tubing.

5.2.3. Putting nut on (Fig. 5-5)

• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube

having completed burr removal.
(not possible to put them on after flaring work)

5.2.4. Flaring work (Fig. 5-6)

• Carry out flaring work using flaring tool as shown at the right.

Dimension

Pipe diameter

A (mm)

(mm)

When the tool for R410A is used

B       (mm)

Clutch type

6.35

0 - 0.5

9.1

9.52

0 - 0.5

13.2

12.7

0 - 0.5

16.6

15.88

0 - 0.5

19.7

Firmly hold copper tube in a die in the dimension shown in the table at above.

5.2.5. Check (Fig. 5-7)

• Compare the flared work with a figure in right side hand.
• If flare is noted to be defective, cut off the flared section and do flaring work again.

5.3. Pipe connection (Fig.5-8)

• Apply a thin coat of refrigeration oil on the seat surface of pipe.
• For connection first align the center, then tighten the first 3 to 4 turns of flare nut.
• Use tightening torque table below as a guideline for indoor unit side union joint section,

and tighten using two wrenches. Excessive tightening damages the flare section.

Copper pipe O.D.

Flare nut O.D.

Tightening torque

(mm)

(mm)

 (N·m)

ø6.35

17

14 - 18

ø9.52

22

34 - 42

ø12.7

26

49 - 61

ø15.88

29

68 - 82

 Warning:

Be careful of flying flare nut! (Internally pressurized)
Remove the flare nut as follows:
1. Loosen the nut until you hear a hissing noise.
2. Do not remove the nut until the gas has been completely released (i.e., hiss-

ing noise stops).

3. Check that the gas has been completely released, and then remove the nut.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied
for indoor unit.
• For tightening use a torque wrench or spanner, and use the same tightening torque

applied for indoor unit.

Refrigerant pipe insulation (Fig. 5-9)

(1) Peel the separator sheet off the accompanying pipe cover, and wrap it around the

refrigerant pipe, making sure that the side which is slit faces upwards.

(2) Be sure to fix both ends of the pipe cover using an attachment band (ensure that

the band’s joint faces upwards).

(3) Stick vinyl tape on the joint positions.

a

Copper tubes

b

Good

c

No good

d

Tilted

e

Uneven

f

Burred

Fig. 5-3

Fig. 5-4

a

Burr

b

Copper tube/pipe

c

Spare reamer

d

Pipe cutter

Fig. 5-5

Fig. 5-6

Fig. 5-7

Fig. 5-8

Fig. 5-9

a

Flare nut

b

Copper tube

a

Flaring tool

b

Die

c

Copper tube

d

Flare nut

e

Yoke

a

f c b

d

e

b

c e

g

h

c

i

a

Indoor unit (main unit)

b

1 Pipe cover

c

2 Band

d

Flare joint

e

Refrigerant pipe and insulating ma-
terial (must be supplied locally)

f

Position the pipe cover so that the end
is in firm contact with the main unit.
Fasten it so that there is no clearance.

g

Allow no clearance

h

Separator sheet

i

Cut off the remainder band

a

Smooth all around

b

Inside is shining without any scratches

c

Even length all around

d

Too much

e

Tilted

f

Scratch on flared plane

g

Cracked

h

Uneven

i

Bad examples

c

b

a

d

e

f

g

h

i

B

+0

-0.4

Содержание SEZ-A12

Страница 1: ...Air Conditioners SEZ A12 A18 A24AR English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ...ient or there is incomplete elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use th...

Страница 3: ...ntaining metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping Units should be installed by licensed contractor accordingly to local code require ment SUZ A18 A24AR A D C A B 42 930 7 100 700 100 29 12 5 120 240 77 5 955 215 25 H J I G J 5027 1016 7 100 700 880 100 40...

Страница 4: ...turdy beams of at least 6 cm square for beam pitch of 90 cm or less or of at least 9cm square for beam pitch of 90 180 cm A Ceiling B Rafter C Beam D Roof beam 4 1 2 Ferro concrete structures Fig 4 2 Secure the suspension bolts using the method shown or use steel or wooden hang ers etc to install the suspension bolts E Use inserts rated at 100 150 kg each procure locally F Suspension bolts M10 3 8...

Страница 5: ... pipe length exceeds 7 m additional refrigerant R410A charge is required The outdoor unit is charged with refrigerant for 7 m pipe length SEZ A12AR 30g m SEZ A18AR 50g m SEZ A24AR 50g m Piping preparation Refrigerant pipes of 3 5 7 10 and 15 m are available as optional items 1 Table below shows the specifications of pipes commercially available 2 Ensure that the 2 refrigerant pipes are well insula...

Страница 6: ... torque mm mm N m ø6 35 17 14 18 ø9 52 22 34 42 ø12 7 26 49 61 ø15 88 29 68 82 Warning Be careful of flying flare nut Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hiss ing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit ...

Страница 7: ...ve After refrigerant pipes are connected and evacuated fully open all stop valves on gas and liquid pipe sides Operating without fully opening lowers the performance and causes trouble Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test Close Open Hexagonal wrench Stop valve 4 to 5 turns Stop valve or the vacuum pump with the function to prevent the back fl...

Страница 8: ...cable and in out connecting cable locally and use remote control cable supplied with the unit 3 Securely connect the power cable and the in out connecting cable and the remote control cable to the terminal blocks 4 Secure the cables with clamps inside the electric component box 5 Attach the electric component cover as it was Fix power supply cable and indoor outdoor cable to control box by using b...

Страница 9: ...ller cord in order to run the remote controller cord from the back then seal the hole with putty Run the remote controller cord through the cut out upper case then seal the cut out notch with putty similarly as above B 1 To lead the remote controller cord from the back of the controller B 2 To run the remote controller cord through the upper portion 3 For direct installation on the wall C Wall D C...

Страница 10: ...e canvas duct for connecting the indoor unit and the duct Fig 8 1 Use fire proof material for the duct parts Make sure that the duct has sufficient heat insulation A Electrical parts box B Canvas duct C Air outlet flange D Air outlet duct E Air filter procure locally F Air outlet grille G Air intake grille H Ceiling I Drainage pan J Air intake K Air outlet L Allow clearance to avoid short cycling ...

Страница 11: ...s 2 3 carefully 3 Please attach filter rail 3 as per the diagram screw 6 Please connect rails 2 3 carefully 4 Seal 6 Upright position here A Control box B Drain pan C Air tight seal Level with edge A A 5 4 C C 4 3 5 6 2 1 Fig 9 3 9 3 Filter rail installation Bottom air intake Fig 9 3 1 Transportation support remove Throw away 2 Please move the plate position Please use the screws removed 3 Please ...

Страница 12: ...r onto rail 3 A Control box B Drain pan D Filter E Rail 2 F Rail 3 Fig 9 4 1 2 B A E D F Fig 9 5 2 1 A E D F A F H G E 9 5 Filter installation points Bottom air intake Fig 9 5 1 Insert the filter into rail 2 2 Hook the filter onto rail 3 3 Bend the clamp to hold the filter A Control box D Filter 1 E Rail 2 F Rail 3 G Bend H Clamp 5 ...

Страница 13: ...e op erational season 10 Test run 10 2 Test run The following 3 methods are available 10 2 1 Using wired remote controller Fig 10 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make ...

Страница 14: ...tity specified for the refrigerating cycle Caution Do not discharge the refrigerant into the atmosphere Take care not to discharge refrigerant into the atmosphere during installa tion reinstallation or repairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If the refrigerant is charged from the gas phase composition change may occur ...

Страница 15: ... SEZ C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous two groups Refrigerant address 01 G Simultaneous three groups Refrigerant address 02 H Simultaneous four groups Refrigerant address 03 I Indoor controller board Refrigerant address 00 Refrigerant address 01 Refrigerant address 02 Refrigerant address 03 The setup at the time shipment...

Страница 16: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN BG79S993H01 The product at hand is based on the following EU regulations Printed in Thailand ...

Отзывы: