background image

13

10.1. Before test run

s

After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M

.

s

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 M

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of

the compressor.

2. If the insulation resistance is below 1 M

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3. After connecting the wires to the compressor, the compressor will start to warm

up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

 after the compressor is warmed

up for two to three hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)

To operate the compressor with refrigerant accumulated in the compressor,
the compressor must be warmed up at least 12 hours to prevent breakdown.

4. If the insulation resistance rises above 1 M

, the compressor is not faulty.

 Caution:

• The compressor will not operate unless the power supply phase connection

is correct.

• Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can result in

severe damage to internal parts. Keep the power switch turned on during the op-
erational season.

10.Test run

10.2. Test run

The following 3 methods are available.

10.2.1. Using wired remote controller (Fig. 10-1)

1

Turn on the power at least 12 hours before the test run.

2

Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

Press the [Mode selection] button and switch to the cooling (or heating) mode.

 Make sure that cold (or warm) wind is blown out.

5

Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

Check operation of the outdoor unit fan.

7

Release test run by pressing the [ON/OFF] button. 

 Stop

8

After the checks, always turn off the power.

A

ON/OFF button

B

Test run display

C

Indoor temperature liquid line temperature display

D

ON/OFF lamp

E

Power display

F

Error code display

Test run remaining time display

G

Set temperature button

H

Mode selection button

I

Fan speed button

M

TEST button

10.3. Self-check

10.3.1. Wired remote controller (Fig. 10-2)

1

Turn on the power.

2

Press the [CHECK] button twice.

3

Set refrigerant address with [TEMP] button if system control is used.

4

Press the [ON/OFF] button to stop the self-check.

A

CHECK button

B

Refrigerant address

C

TEMP. button

D

IC:

Indoor unit

OC: Outdoor unit

E

Check code

ON/OFF 

CENTRALLY CONTROLLED

ERROR CODE

CLOCK

ON

OFF

˚C

CHECK

CHECK MODE

FILTER

TEST RUN

FUNCTION

˚C

1Hr.

NOT AVAILABLE

STAND BY 
DEFROST

FILTER

CHECK TEST

TEMP.

TIMER SET

D

E

F

H

I

M

G

C

B

A

Fig. 10-1

ON/OFF 

CHECK

FILTER

CHECK TEST

TEMP.

TIMER SET

B

C

A

STAND BY 
DEFROST

INDOOR UNIT

ADDRESS NO

ERROR CODE

OA UNIT ADDRESS NO

CENTRALLY CONTROLLED

CLOCK

ON OFF

˚C

1Hr.

NOT AVAILABLE

˚C

CHECK MODE

FILTER

CHECK

FUNCTION

ERROR CODE

OA UNIT ADDRESS NO

STAND BY 
DEFROST

INDOOR UNIT

ADDRESS NO

CENTRALLY CONTROLLED

CLOCK

ON OFF

˚C

1Hr.

NOT AVAILABLE

˚C

CHECK MODE

FILTER

CHECK

FUNCTION

a)

D

E

• For description of each check code, refer to the following table.

1

 Check code

Symptom

5101

Room temperature thermistor error

5102

RT12, 13 thermistor error

2503

Drain sensor error

2502

Drain pump error

1503

Freezing safeguard operation

0405, 1501, 4210, 5102

Outdoor unit error

6831~6834

Signal error between remote controller and indoor units

6800

Communication error between indoor and outdoor units

8000

No alarm history

F F F F

No unit

• On wired remote controller

1

Check code displayed in the LCD.

Fig. 10-2

Содержание SEZ-A12

Страница 1: ...Air Conditioners SEZ A12 A18 A24AR English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ...ient or there is incomplete elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use th...

Страница 3: ...ntaining metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping Units should be installed by licensed contractor accordingly to local code require ment SUZ A18 A24AR A D C A B 42 930 7 100 700 100 29 12 5 120 240 77 5 955 215 25 H J I G J 5027 1016 7 100 700 880 100 40...

Страница 4: ...turdy beams of at least 6 cm square for beam pitch of 90 cm or less or of at least 9cm square for beam pitch of 90 180 cm A Ceiling B Rafter C Beam D Roof beam 4 1 2 Ferro concrete structures Fig 4 2 Secure the suspension bolts using the method shown or use steel or wooden hang ers etc to install the suspension bolts E Use inserts rated at 100 150 kg each procure locally F Suspension bolts M10 3 8...

Страница 5: ... pipe length exceeds 7 m additional refrigerant R410A charge is required The outdoor unit is charged with refrigerant for 7 m pipe length SEZ A12AR 30g m SEZ A18AR 50g m SEZ A24AR 50g m Piping preparation Refrigerant pipes of 3 5 7 10 and 15 m are available as optional items 1 Table below shows the specifications of pipes commercially available 2 Ensure that the 2 refrigerant pipes are well insula...

Страница 6: ... torque mm mm N m ø6 35 17 14 18 ø9 52 22 34 42 ø12 7 26 49 61 ø15 88 29 68 82 Warning Be careful of flying flare nut Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hiss ing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit ...

Страница 7: ...ve After refrigerant pipes are connected and evacuated fully open all stop valves on gas and liquid pipe sides Operating without fully opening lowers the performance and causes trouble Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test Close Open Hexagonal wrench Stop valve 4 to 5 turns Stop valve or the vacuum pump with the function to prevent the back fl...

Страница 8: ...cable and in out connecting cable locally and use remote control cable supplied with the unit 3 Securely connect the power cable and the in out connecting cable and the remote control cable to the terminal blocks 4 Secure the cables with clamps inside the electric component box 5 Attach the electric component cover as it was Fix power supply cable and indoor outdoor cable to control box by using b...

Страница 9: ...ller cord in order to run the remote controller cord from the back then seal the hole with putty Run the remote controller cord through the cut out upper case then seal the cut out notch with putty similarly as above B 1 To lead the remote controller cord from the back of the controller B 2 To run the remote controller cord through the upper portion 3 For direct installation on the wall C Wall D C...

Страница 10: ...e canvas duct for connecting the indoor unit and the duct Fig 8 1 Use fire proof material for the duct parts Make sure that the duct has sufficient heat insulation A Electrical parts box B Canvas duct C Air outlet flange D Air outlet duct E Air filter procure locally F Air outlet grille G Air intake grille H Ceiling I Drainage pan J Air intake K Air outlet L Allow clearance to avoid short cycling ...

Страница 11: ...s 2 3 carefully 3 Please attach filter rail 3 as per the diagram screw 6 Please connect rails 2 3 carefully 4 Seal 6 Upright position here A Control box B Drain pan C Air tight seal Level with edge A A 5 4 C C 4 3 5 6 2 1 Fig 9 3 9 3 Filter rail installation Bottom air intake Fig 9 3 1 Transportation support remove Throw away 2 Please move the plate position Please use the screws removed 3 Please ...

Страница 12: ...r onto rail 3 A Control box B Drain pan D Filter E Rail 2 F Rail 3 Fig 9 4 1 2 B A E D F Fig 9 5 2 1 A E D F A F H G E 9 5 Filter installation points Bottom air intake Fig 9 5 1 Insert the filter into rail 2 2 Hook the filter onto rail 3 3 Bend the clamp to hold the filter A Control box D Filter 1 E Rail 2 F Rail 3 G Bend H Clamp 5 ...

Страница 13: ...e op erational season 10 Test run 10 2 Test run The following 3 methods are available 10 2 1 Using wired remote controller Fig 10 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make ...

Страница 14: ...tity specified for the refrigerating cycle Caution Do not discharge the refrigerant into the atmosphere Take care not to discharge refrigerant into the atmosphere during installa tion reinstallation or repairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If the refrigerant is charged from the gas phase composition change may occur ...

Страница 15: ... SEZ C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous two groups Refrigerant address 01 G Simultaneous three groups Refrigerant address 02 H Simultaneous four groups Refrigerant address 03 I Indoor controller board Refrigerant address 00 Refrigerant address 01 Refrigerant address 02 Refrigerant address 03 The setup at the time shipment...

Страница 16: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN BG79S993H01 The product at hand is based on the following EU regulations Printed in Thailand ...

Отзывы: