5. Refrigerant piping work

5.1. Refrigerant pipe (Fig. 5-1)

Maximum difference between heights of indoor unit and outdoor unit, the length of
refrigerant piping and the number of bends in piping are within limits shown below.

Models

(A) Pipe length

(B) Height

(C) Number of

(one way)

difference

bends (one way)

SEZ-A12AR

max. 20 m

max. 12 m

max. of 10

SEZ-A18AR

max. 30 m

max. 15 m

max. of 10

SEZ-A24AR

max. 30 m

max. 15 m

max. of 10

*1: Height difference limitations are binding regardless of which unit, indoor or out-

door, is positioned higher.

Avoid the following places for installation where air conditioner trouble is liable to
occur.
• Where there is too much oil such as for machine or cooking.
• Salty environment as seaside areas.
• Hot-spring areas.
• Where sulfide gas exists.
• Other special atmospheric areas.
• This unit has flared connections on both indoor and outdoor sides. (Fig. 5-2)
• Refrigerant pipes are used to connect the indoor and outdoor units as shown in the

figure below.

• Insulate both refrigerant and drainage piping completely to prevent condensation.
• Refrigerant adjustment … If pipe length exceeds 7 m, additional refrigerant (R410A)

charge is required.
(The outdoor unit is charged with refrigerant for 7 m pipe length.)

SEZ-A12AR:30g/m
SEZ-A18AR:50g/m
SEZ-A24AR:50g/m

Piping preparation

• Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.

(1) Table below shows the specifications of pipes commercially available.

(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.

(3) Refrigerant pipe bending radius must be 10 cm or more.

 Caution:

Using careful insulation of specified thickness. Excessive thickness prevents
storage behind the indoor unit and smaller thickness causes dew drippage.

Ø6.35

SEZ-A12:Ø9.52
SEZ-A18:Ø12.7
SEZ-A24:Ø15.88

1

2

b

(C)

(B)

(A)

a

Fig. 5-1

Fig. 5-2

Pipe length

7 m

maximum

No additional

charge required

Refrigerant

to be added

Additional

charge required

Exceeding

7 m

a

Indoor unit

b

Outdoor unit

1

Indoor unit

2

Outdoor unit

Pipe

For liquid

For gas

For liquid

For gas

For liquid

For gas

Outside diameter

mm

inch

6.35

1/4

9.52

3/8

6.35

1/4

12.7

1/2

6.35

1/4

15.88

5/8

Model

SEZ-A12AR

SEZ-A18AR

SEZ-A24AR

Insulation

material

Heat resisting

foam plastic

0.045 specific

gravity

Insulation

thickness

8 mm

8 mm

8 mm

8 mm

8 mm

8 mm

Min wall

thickness

0.8 mm

0.8 mm

0.8 mm

0.8 mm

0.8 mm

1.0 mm

Содержание SEZ-A12

Страница 1: ...Air Conditioners SEZ A12 A18 A24AR English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ...ient or there is incomplete elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use th...

Страница 3: ...ntaining metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping Units should be installed by licensed contractor accordingly to local code require ment SUZ A18 A24AR A D C A B 42 930 7 100 700 100 29 12 5 120 240 77 5 955 215 25 H J I G J 5027 1016 7 100 700 880 100 40...

Страница 4: ...turdy beams of at least 6 cm square for beam pitch of 90 cm or less or of at least 9cm square for beam pitch of 90 180 cm A Ceiling B Rafter C Beam D Roof beam 4 1 2 Ferro concrete structures Fig 4 2 Secure the suspension bolts using the method shown or use steel or wooden hang ers etc to install the suspension bolts E Use inserts rated at 100 150 kg each procure locally F Suspension bolts M10 3 8...

Страница 5: ... pipe length exceeds 7 m additional refrigerant R410A charge is required The outdoor unit is charged with refrigerant for 7 m pipe length SEZ A12AR 30g m SEZ A18AR 50g m SEZ A24AR 50g m Piping preparation Refrigerant pipes of 3 5 7 10 and 15 m are available as optional items 1 Table below shows the specifications of pipes commercially available 2 Ensure that the 2 refrigerant pipes are well insula...

Страница 6: ... torque mm mm N m ø6 35 17 14 18 ø9 52 22 34 42 ø12 7 26 49 61 ø15 88 29 68 82 Warning Be careful of flying flare nut Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hiss ing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit ...

Страница 7: ...ve After refrigerant pipes are connected and evacuated fully open all stop valves on gas and liquid pipe sides Operating without fully opening lowers the performance and causes trouble Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test Close Open Hexagonal wrench Stop valve 4 to 5 turns Stop valve or the vacuum pump with the function to prevent the back fl...

Страница 8: ...cable and in out connecting cable locally and use remote control cable supplied with the unit 3 Securely connect the power cable and the in out connecting cable and the remote control cable to the terminal blocks 4 Secure the cables with clamps inside the electric component box 5 Attach the electric component cover as it was Fix power supply cable and indoor outdoor cable to control box by using b...

Страница 9: ...ller cord in order to run the remote controller cord from the back then seal the hole with putty Run the remote controller cord through the cut out upper case then seal the cut out notch with putty similarly as above B 1 To lead the remote controller cord from the back of the controller B 2 To run the remote controller cord through the upper portion 3 For direct installation on the wall C Wall D C...

Страница 10: ...e canvas duct for connecting the indoor unit and the duct Fig 8 1 Use fire proof material for the duct parts Make sure that the duct has sufficient heat insulation A Electrical parts box B Canvas duct C Air outlet flange D Air outlet duct E Air filter procure locally F Air outlet grille G Air intake grille H Ceiling I Drainage pan J Air intake K Air outlet L Allow clearance to avoid short cycling ...

Страница 11: ...s 2 3 carefully 3 Please attach filter rail 3 as per the diagram screw 6 Please connect rails 2 3 carefully 4 Seal 6 Upright position here A Control box B Drain pan C Air tight seal Level with edge A A 5 4 C C 4 3 5 6 2 1 Fig 9 3 9 3 Filter rail installation Bottom air intake Fig 9 3 1 Transportation support remove Throw away 2 Please move the plate position Please use the screws removed 3 Please ...

Страница 12: ...r onto rail 3 A Control box B Drain pan D Filter E Rail 2 F Rail 3 Fig 9 4 1 2 B A E D F Fig 9 5 2 1 A E D F A F H G E 9 5 Filter installation points Bottom air intake Fig 9 5 1 Insert the filter into rail 2 2 Hook the filter onto rail 3 3 Bend the clamp to hold the filter A Control box D Filter 1 E Rail 2 F Rail 3 G Bend H Clamp 5 ...

Страница 13: ...e op erational season 10 Test run 10 2 Test run The following 3 methods are available 10 2 1 Using wired remote controller Fig 10 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make ...

Страница 14: ...tity specified for the refrigerating cycle Caution Do not discharge the refrigerant into the atmosphere Take care not to discharge refrigerant into the atmosphere during installa tion reinstallation or repairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If the refrigerant is charged from the gas phase composition change may occur ...

Страница 15: ... SEZ C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous two groups Refrigerant address 01 G Simultaneous three groups Refrigerant address 02 H Simultaneous four groups Refrigerant address 03 I Indoor controller board Refrigerant address 00 Refrigerant address 01 Refrigerant address 02 Refrigerant address 03 The setup at the time shipment...

Страница 16: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN BG79S993H01 The product at hand is based on the following EU regulations Printed in Thailand ...

Отзывы: