5. Refrigerant piping work

5.4. Purging procedures leak test

PURGING PROCEDURES

Connect the refrigerant pipes (both the liquid and gas pipes) between the indoor
and the outdoor units.

Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe.
(The stop valve will not work in its initial state fresh out of the factory (totally closed
with cap on).)

Connect the gage manifold valve and the vacuum pump to the service port of the
stop valve on the gas pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gage manifold valve, then close the gage manifold valve,
and stop the vacuum pump.

Leave it as is for one or two minutes. Make sure the pointer of the gage manifold
valve remains in the same position. Confirm that the pressure gage show -0.101MPa
(-760 mmHg)

Pipe length :

7 m maximum

No gas charge is needed.

Pipe length exceeding 7 m

Charge the prescribed

amount of gas.

Remove the gage manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on
gas and liquid pipe sides.
Operating without fully opening lowers the performance and causes trouble.

Tighten the cap to the service port to obtain the initial status.

Retighten the cap

Leak test

*Close

*Open

Hexagonal wrench

Stop valve

*4 to 5 turns

Stop valve

(or the vacuum
pump with the
function to
prevent the back
flow)

Gauge manifold
valve (for R410A)

Pressure gauge
    (for R410A)

Compound pressure
gauge (for R410A)

-0.101MPa
(-760 mmHg)

Handle
Low

Handle High

Window

Charge hose
(for R410A)

Vacuum
pump

Adapter for
preventing
the back flow

Charge hose
(for R410A)

Service port

Stop
valve

6. Drainage piping work

Fig. 6-1

6.1. Drainage pipe connection (Fig. 6-1)

Indoor unit’s drainage pipe

• The drainage pipe should be arranged so that the discharge end is lower than the

other end, as shown in the figure opposite.

• Place the trap outside the unit.
• After connecting the drainage pipe, make sure that water is discharged properly

and that there are no leaks.

A

Drainage piping connection 1 RP male.

B

Trap

Outdoor unit drainage pipe connection

When drainage piping is necessary, use the drain pan (supplied as an option).

A

B

H

1

H

2

H

1

 : 50 mm or more

H

2

 : 1/2 H

1

 or more

Содержание SEZ-A12

Страница 1: ...Air Conditioners SEZ A12 A18 A24AR English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ...ient or there is incomplete elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use th...

Страница 3: ...ntaining metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping Units should be installed by licensed contractor accordingly to local code require ment SUZ A18 A24AR A D C A B 42 930 7 100 700 100 29 12 5 120 240 77 5 955 215 25 H J I G J 5027 1016 7 100 700 880 100 40...

Страница 4: ...turdy beams of at least 6 cm square for beam pitch of 90 cm or less or of at least 9cm square for beam pitch of 90 180 cm A Ceiling B Rafter C Beam D Roof beam 4 1 2 Ferro concrete structures Fig 4 2 Secure the suspension bolts using the method shown or use steel or wooden hang ers etc to install the suspension bolts E Use inserts rated at 100 150 kg each procure locally F Suspension bolts M10 3 8...

Страница 5: ... pipe length exceeds 7 m additional refrigerant R410A charge is required The outdoor unit is charged with refrigerant for 7 m pipe length SEZ A12AR 30g m SEZ A18AR 50g m SEZ A24AR 50g m Piping preparation Refrigerant pipes of 3 5 7 10 and 15 m are available as optional items 1 Table below shows the specifications of pipes commercially available 2 Ensure that the 2 refrigerant pipes are well insula...

Страница 6: ... torque mm mm N m ø6 35 17 14 18 ø9 52 22 34 42 ø12 7 26 49 61 ø15 88 29 68 82 Warning Be careful of flying flare nut Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hiss ing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit ...

Страница 7: ...ve After refrigerant pipes are connected and evacuated fully open all stop valves on gas and liquid pipe sides Operating without fully opening lowers the performance and causes trouble Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test Close Open Hexagonal wrench Stop valve 4 to 5 turns Stop valve or the vacuum pump with the function to prevent the back fl...

Страница 8: ...cable and in out connecting cable locally and use remote control cable supplied with the unit 3 Securely connect the power cable and the in out connecting cable and the remote control cable to the terminal blocks 4 Secure the cables with clamps inside the electric component box 5 Attach the electric component cover as it was Fix power supply cable and indoor outdoor cable to control box by using b...

Страница 9: ...ller cord in order to run the remote controller cord from the back then seal the hole with putty Run the remote controller cord through the cut out upper case then seal the cut out notch with putty similarly as above B 1 To lead the remote controller cord from the back of the controller B 2 To run the remote controller cord through the upper portion 3 For direct installation on the wall C Wall D C...

Страница 10: ...e canvas duct for connecting the indoor unit and the duct Fig 8 1 Use fire proof material for the duct parts Make sure that the duct has sufficient heat insulation A Electrical parts box B Canvas duct C Air outlet flange D Air outlet duct E Air filter procure locally F Air outlet grille G Air intake grille H Ceiling I Drainage pan J Air intake K Air outlet L Allow clearance to avoid short cycling ...

Страница 11: ...s 2 3 carefully 3 Please attach filter rail 3 as per the diagram screw 6 Please connect rails 2 3 carefully 4 Seal 6 Upright position here A Control box B Drain pan C Air tight seal Level with edge A A 5 4 C C 4 3 5 6 2 1 Fig 9 3 9 3 Filter rail installation Bottom air intake Fig 9 3 1 Transportation support remove Throw away 2 Please move the plate position Please use the screws removed 3 Please ...

Страница 12: ...r onto rail 3 A Control box B Drain pan D Filter E Rail 2 F Rail 3 Fig 9 4 1 2 B A E D F Fig 9 5 2 1 A E D F A F H G E 9 5 Filter installation points Bottom air intake Fig 9 5 1 Insert the filter into rail 2 2 Hook the filter onto rail 3 3 Bend the clamp to hold the filter A Control box D Filter 1 E Rail 2 F Rail 3 G Bend H Clamp 5 ...

Страница 13: ...e op erational season 10 Test run 10 2 Test run The following 3 methods are available 10 2 1 Using wired remote controller Fig 10 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make ...

Страница 14: ...tity specified for the refrigerating cycle Caution Do not discharge the refrigerant into the atmosphere Take care not to discharge refrigerant into the atmosphere during installa tion reinstallation or repairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If the refrigerant is charged from the gas phase composition change may occur ...

Страница 15: ... SEZ C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous two groups Refrigerant address 01 G Simultaneous three groups Refrigerant address 02 H Simultaneous four groups Refrigerant address 03 I Indoor controller board Refrigerant address 00 Refrigerant address 01 Refrigerant address 02 Refrigerant address 03 The setup at the time shipment...

Страница 16: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN BG79S993H01 The product at hand is based on the following EU regulations Printed in Thailand ...

Отзывы: