![Mitsubishi Electric RD77GF16 Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/mitsubishi-electric/rd77gf16/rd77gf16_user-manual_1811854060.webp)
58
1 FUNCTIONS
1.5 IP Packet Transfer Function
■
Setting in the Ethernet adapter module 2 (station No.1)
Use the configuration tool to set the IP address.
1.
Set the IP address in the Ethernet adapter module 2 (Ethernet part) as follows.
Setting item tree
NZ2GF-ETB
[Parameter]
"Ethernet"
2.
The IP address setting is not required for the Ethernet adapter module 2 (CC-Link IE Field Network part).
The network address set in the master station 2 (station No.0) is automatically assigned.
3.
The CC-Link IE Field Network gateway setting is not required for the Ethernet adapter module 2.
Because the network address of the request destination (Ethernet adapter module 1) is the same as that of the master station,
setting only the communication path in the routing parameters allows communications to be performed with the request
destination.
4.
Write the set parameters to the Ethernet adapter module 2.