3 - 37 3 - 37
MELSEC-Q
3 SPECIFICATIONS
(2) Master Function Transmit Data (address: 0900
H
to 09FF
H
/2304 to
2559)
Data to be sent to each slave node are set in this area.
Data are aligned on word boundaries of slave nodes and stored as shown below.
For double-word data, the low word is stored first and then the high word.
When the number of byte input modules is an odd number, one byte of an empty
area is inserted.
The following is an example.
<Example>
1st node - Number of byte output modules = 3
Number of word output modules = 2
Number of double-word output modules = 2
2nd node - Number of byte output modules = 1
3rd node - Number of byte output modules = 1
Buffer memory
address
0900
H
0901
H
0902
H
0903
H
0904
H
0905
H
0906
H
0907
H
0908
H
0909
H
When the number of byte input
modules is an odd number,one
byte of an empty area is inserted.
Output data of the 1st node
Output data of the 2nd node
Output data of the 3rd node
2nd byte module
1st byte module
3rd byte module
Empty
1st word module
2nd word module
Low word of
the 1st double-word module
High word of
the 1st double-word module
Low word of
the 2nd double-word module
High word of
the 2nd double-word module
1st byte module
1st byte module
Empty
Empty