3 - 35 3 - 35
MELSEC-Q
3 SPECIFICATIONS
(c) Contents of Parameters for Master Function set by auto configuration
An execution of auto configuration reads parameters of each slave node and
writes them to Parameters for Master Function (address: 01D4
H
to 03CF
H
).
Set values can be changed in sequence programs or GX Configurator-DN.
Table 3.26 Auto configuration settings
Buffer memory
address (Hex.)
Item Description
01D8
H
1st slave
node
Node No. and message
group
Low byte: Node No. (MAC ID) of the 1st slave node
00
H
to 3F
H
(0 to 63)
High byte: 01
H
Node that supports UCMM and uses any of message
groups 3, 2, and 1.
03
H
Node that supports UCMM and uses message group 1
04
H
Node that does not support UCMM (Group 2 only
server)
01D9
H
Connection
type
Connection type for I/O communication.
0001
H
= Polling
0002
H
= Bit strobe
0004
H
= Change of state
0008
H
= Cyclic
01DA
H
Number of byte modules
Low byte: Number of input byte modules
High byte: Number of output byte modules (set in hexadecimal)
Eight bit modules (8 points) are counted as one byte module.
01DB
H
Number of word modules
Low byte: Number of input word modules
High byte: Number of output word modules (set in hexadecimal)
01DC
H
Number of double-word
modules
Low byte: Number of input double-word modules
High byte: Number of output double-word modules (set in hexadecimal)
01DD
H
Expected packet rate
Default value is stored.
(0000
H
: 200ms)
01DE
H
Watchdog timeout action
Default value is stored. (0000
H
: Timeout)
01DF
H
Production inhibit time
Default value is stored. (0000
H
: 10ms)
01E0
H
to
03CF
H
Settings for 2nd
to 63rd slave nodes
Same as those for 1st slave node