3 - 34 3 - 34
MELSEC-Q
3 SPECIFICATIONS
(2) Auto Configuration Operation Setting (address: 03F0
H
/1008)
The operation of auto configuration is set in this area.
For the execution timing, refer to Section 7.3 (2).
(a) Setting details
1) High byte
Set an auto configuration type.
00
H
: All configuration (Default)
01
H
: Add configuration
2) Low byte
Set the maximum detection node No.
00
H
to 3F
H
(0 to 63) (Default: 3F
H
)
(b) Operation of auto configuration
1) When "All configuration" is set:
• Clears all of Parameters for Master Function (address: 01D4
H
to
03CF
H
). (Except the Constant scan area)
• Detects all of the slave nodes within a range from node 0 to the
maximum detection node on the network.
• Stores parameters of the detected slave nodes into the "Parameters
for Master Function" area (address: 01D4
H
to 03CF
H
).
2) When "Add configuration" is set:
• Detects all of the slave nodes within a range from node 0 to the
maximum detection node on the network, except for slave nodes
that have been already set to the master node.
• Stores parameters of the detected slave nodes into the area after
the preset area in Parameters for Master Function (address: 01D4
H
to 03CF
H
).
Note that the area after the parameter storing area is not cleared.