59
1
2
3
4
5
M
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10 to 30°C)
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20°C)
Thermistor (TH3)
<Liquid>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<2-phase pipe>
Thermistor (TH7)
<Ambient>
Thermistor (TH8)
<Heat sink>
Thermistor (TH33)
<Comp. surface>
Normal
160 to 410 k
"
4.3 to 9.6 k
"
39 to 105 k
"
TH4, TH33
TH3
TH6
TH7
TH8
Abnormal
Open or short
Normal
Red - White
Red - Orange
Red - Yellow
Red - Blue
Abnormal
46±4
"
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20°C)
Solenoid valve coil
<4-way valve>
(21S4)
Motor for compressor
(MC)
Linear expansion valve
(LEV-A/LEV-B)
For
ZM
35–71
Normal
Abnormal
Open or short
Abnormal
Open or short
Refer to “5-2. COMPRESSOR TECHNICAL DATA”.
ZM35–71
Open or short
Refer to the next page.
Fan motor(MF1,MF2)
2350±170
"
Measure the resistance between the terminals with a tester.
(Winding temperature 20°C)
Normal
W
V
U
Red
Blue
Orange
Yellow
White
10-6. HOW TO CHECK THE PARTS