*2 ‘Power failure automatic recovery’ can be set by either remote controller or this DIP SW. If one of them is set to ON, ‘Auto
recovery’ activates. Please set “Auto recovery” basically by remote controller because all units do not have DIP SW.
Please refer to the indoor unit installation manual.
*3
SW7-1 is setting change over of Demand/Low noise. It is effective only in case of external input.
(Local wiring is necessary. Refer to next page: Special function)
*4
Please do not use SW7-3 to 7-6 usually. Trouble might be caused by the usage condition.
*5
With this switch setting, the capacity decreases up to 30% under peak load condition.
*6
SW6-1 to 3: Function Switch
Type of
Switch
Switch No.
Function
Action by the switch operation
Effective timing
ON
OFF
DIP
switch
SW5
1
No function
—
—
—
2
Power failure
automatic recovery *2
Auto recovery
No auto recovery
When power supply ON
3,4,5,6
No function
—
—
—
SW7
*4
1
Mode select *3
Demand function
Low noise mode
Always
2
No function
—
—
—
3
Max Hz setting (cooling)
Max Hz (cooling)
o
0.8
Normal
Always
4
Max Hz setting (heating) Max Hz (heating)
o
0.8
Normal
Always
5
Breaker capacity setting *5
Decrease capacity
Normal
When power supply ON
6
Defrost setting
For high humidity
Normal
Always
SW8
1
No function
—
—
—
2
No function
—
—
—
3
No function
—
—
—
SW9
1
No function
—
—
—
2
Function switch
Valid
Normal
Always
3,4
No function
—
—
—
SW6
1
2
No function
3
4
Model select
5
6
7
8
1 2 3
6
4
7 8
OFF
ON
35V
MODEL
SW6*
6
1 2 3
6
4
7
5
8
OFF
ON
50V
1 2 3
6
4
7
4 5
8
OFF
ON
60V
1 2 3
6
4
7
4 5
8
OFF
ON
71V
5
■
is the switch position.