45
(
)
Check Code Abnormal points and detection method
Case
Judgment and action
EF
(6607
or
6608)
Non defined check code
This code is displayed when non
-
defined
check code is received.
1
Noise has entered transmission wire
of remote controller.
2
Noise has entered indoor/ outdoor
unit connecting wire.
3
Outdoor unit is not a series of power-
inverter.
12
Turn the power off, and on again to
check.
Replace indoor controller board or
outdoor controller circuit board if
abnormality is displayed again.
3
Replace outdoor unit with power-inverter
type outdoor unit.
Ed
(0403)
Serial communication error
1
Abnormal if serial communication
between outdoor controller circuit board
and outdoor power circuit board is defec-
tive.
1
Breaking of wire or contact failure of
connector CN2 between the outdoor
controller circuit board and the
outdoor power circuit board
2
Breaking of wire or contact failure of
connector CN4 between the outdoor
controller circuit board and the
outdoor power circuit board
3
Defective communication circuit of
outdoor power circuit board
4
Defective communication circuit of
outdoor controller circuit board for
outdoor power circuit board
12
Check connection of each connector
CN2 and CN4 between the outdoor
controller circuit board and the outdoor
power circuit board.
3
Replace outdoor power circuit board.
4
Replace outdoor controller circuit board.
2
Abnormal if communication between
outdoor controller circuit board and
M-NET board is not available.
1
Breaking of wire or contact failure of
connector between outdoor controller
circuit board and M-NET board
2
Contact failure of M-NET board
power supply line
3
Noise has entered into M-NET trans-
mission wire.
1
Check disconnection, looseness, or break-
ing of connection wire between outdoor
controller circuit board (CNMNT) and
M-NET board (CN5).
2
Check disconnection, looseness, or break-
ing of connection wire between outdoor
controller circuit board (CNMNT) and
M-NET board (CND).
3
Check M-NET transmission wiring method.
EE
Abnormal if a connection of indoor unit and
outdoor unit which uses different refrigerant
is detected.
1
Unauthorized connection of indoor
unit and outdoor unit
Connections other than below combi-
nation are not authorized;
Outdoor unit: Models with R32 refrigerant
Indoor unit
:
Floor standing type
indoor unit (PSA-KA)
1
Alter the connection referring to the com-
bination as shown in the “case” column.
P8
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe
temperature is not in the cooling range
3 minutes after compressor starts and
6 minutes after the liquid or condenser/
evaporator pipe is out of cooling range.
Note 1
:
It takes at least 9 minutes to detect.
Note 2: Abnormality P8 is not detected in
drying mode.
Cooling range: Indoor pipe temperature
(TH2 or TH5) – intake temperature
(TH1)
[
−3
:
TH: Lower temperature between liquid pipe
temperature and condenser/evaporator
temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in
heating range within 20 minutes.
Note 3: It takes at least 27 minutes to
detect abnormality.
Note 4: It excludes the period of defrosting
(Detection restarts when defrosting
mode is over)
Heating range: 3
:
[
(Condenser/
Evaporator temperature (TH5) –
intake temperature (TH1))
1
Slight temperature difference
between indoor room temperature
and pipe <liquid or condenser/
evaporator> temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser/evaporator>
thermistor
• Defective refrigerant circuit
2
Converse connection of extension
pipe (on plural units connection)
3
Converse wiring of indoor/outdoor
unit connecting wire (on plural units
connection)
4
Defective detection of indoor room
temperature and pipe <condenser/
evaporator> temperature thermistor
5
Stop valve is not opened completely.
1
–
4
Check pipe <liquid or condenser/
evaporator> temperature with room
temperature display on remote
controller and outdoor controller circuit
board.
Pipe <liquid or condenser / evapora-
tor> temperature display is indicated
by setting SW2 of outdoor controller
circuit board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
‘A-Control Service Tool (PAC-SK52ST)’.
1
2
3
4
5
6
ON
OFF
1
2
3
4
5
6
ON
OFF
1
2
3
4
5
6
ON
OFF
1
2
3
4
5
6
ON
OFF
A-Control Service Tool SW2 setting
Temperature display of indoor liquid pipe
Indoor 1
Temperature display of indoor liquid pipe
Indoor 2
Temperature display of indoor condenser/
evaporator pipe Indoor 1
Temperature display of indoor condenser/
evaporator pipe Indoor 2
23
Check converse connection of exten-
sion pipe or converse wiring of indoor/
outdoor unit connecting wire.
OCH653