106
OPERATING PROCEDURE
PHOTOS
Photo 13
Photo 14
Compressor
(MC)
Valve bed
Separator
Separator
fixing screw
Compressor
fixing nut
Accumul
ator
Accumulator
Outlet
Inlet
12. Removing the compressor (MC)
(1) Remove the service panel. (See photo 1.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the conduit cover and cord cover.
(See photo 2.)
(5) Remove the back panel. (See photo 1.)
(6) Remove the electrical parts box. (See photo 5.)
(7) Remove 3 separator fixing screws (4
✕
10) and remove
the separator.
(8) Collect the refrigerant.
(9) Remove 3 compressor fixing nuts by using spanner or
adjustable wrench.
(10) Remove the welded pipe of motor for compressor inlet
and outlet.
Note: Collect refrigerant without spreading it in the air.
Accumulator leg
fixing screw
Accumulator leg
13. Removing the accumulator
(1) Remove the service panel. (See photo1.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the conduit cover and cord cover. (See photo 2.)
(5) Remove the back panel. (See photo 1.)
(6) Remove the electrical parts box. (See photo 5.)
(7) Collect the refrigerant.
(8) Remove 2 welded pipes of accumulator inlet and outlet.
(9) Remove 2 accumulator leg fixing screws (4
✕
10).
(10) Remove the accumulator together with the receiver leg.
Note: Collect refrigerant without spreading it in the air.
OC367C--4.qxp 07.6.20 0:58 PM Page 106
Содержание PUY-A12NHA
Страница 120: ...120 FUNCTIONAL PARTS PUZ A18NHA PUY A12NHA PUY A18NHA 1 2 3 4 5 6 7 8 9 10 11 12 23 13 16 17 15 18 19 20 22 21 14 ...
Страница 124: ...124 FUNCTIONAL PARTS PUZ A42NHA PUY A42NHA 12 3 5 6 10 2 9 1 7 8 11 13 14 15 16 17 19 20 21 22 23 24 25 26 27 28 4 1 18 ...
Страница 135: ...135 ...