41
TCH091
8-1-3. Countermeasures for Error During Test Run
• If a problem occurs during test run, a code number will appear on the remote controller (or LED on the outdoor unit), and the
air conditioning system will automatically cease operating.
Determine the nature of the abnormality and apply corrective measures.
1 2 3 4 5 6 7 8
[Example]
When the compressor and
SV1 are turned during cooling
operation.
Bit
Indication
1
Compressor
operated
2
52C
3
21S4
4
SV1
5
(SV2)
6
SV3
7
—
8
Always lit
Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1, SWP2) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
Check
code
(2 digits)
Check
code
(4 digits)
Trouble
Detected Unit
Remarks
Indoor
Outdoor
Remote
Controller
Ed
0403
Serial communication error
Outdoor unit outdoor multi controller circuit board
– Power circuit board communication trouble
U2
1102
Compressor temperature trouble
Check delay code 1202
UE
1302 High pressure trouble or High compressor temperature (TRS) trouble
Check delay code 1402
U7
1500 Superheat due to low discharge temperature trouble
Check delay code 1600
U2
1501
Refrigerant shortage trouble
Check delay code 1601
Closed valve in cooling mode
Check delay code 1501
P6
1503
Freeze protection of Branch box or Indoor unit
EF
1508 4-way valve trouble in heating mode
Check delay code 1608
PA
2500 Water leakage
P5
2502 Drain overflow protection
P4
2503
Drain sensor trouble
UF
4100 Compressor current interruption (locked compressor)
Check delay code 4350
Pb
4114 Fan trouble (indoor)
UP
4210 Compressor overcurrent interruption/failure in 12 VDC power
supply circuit on power circuit board
U9
4220 Undervoltage/overvoltage/PAM error/L1 open phase/power
synchronization signal error
Check delay code 4320
U5
4230 Heat sink temperature trouble
Check delay code 4330
U6
4250 Power module trouble or overcurrent trouble
Check delay code 4350
U8
4400 Fan trouble (outdoor)
Check delay code 4500
U3
5101
Air inlet thermistor (TH21) open/short or
Compressor temperature thermistor (TH4) open/short
Check delay code 1202
U4
5102
Liquid pipe temperature thermistor (TH22) open/short or
Suction pipe temperature thermistor (TH6) open/short
Check delay code 1211
U4
5103 Gas pipe temperature thermistor (TH23) open/short
U4
5105 Outdoor liquid pipe temperature thermistor (TH3) open/short
Check delay code 1205
U4
5106 Ambient thermistor (TH7) open/short
Check delay code 1221
U4
5109 HIC pipe temperature thermistor (TH2) open/short
Check delay code 1222
U4
5110 Heat sink temperature thermistor (TH8) open/short
Check delay code 1214
F5
5201 High pressure sensor (63HS) trouble
Check delay code 1402
F3
5202 Low pressure sensor (63LS) trouble
Check delay code 1400
UH
5300
Current sensor trouble
Check delay code 4310
P4
5701 Contact failure of drain float switch
A0
6600
Duplex address error
Only M-NET Remote controller is detected.
A2
6602 Transmission processor hardware error
Only M-NET Remote controller is detected.
A3
6603
Transmission bus BUSY error
Only M-NET Remote controller is detected.
A6
6606 Signal communication error with transmission processor
Only M-NET Remote controller is detected.
A7
6607
No ACK error
Only M-NET Remote controller is detected.
A8
6608
No response frame error
Only M-NET Remote controller is detected.
E0/E4
6831 MA communication receive error (no receive signal)
Only MA Remote controller is detected.
E3/E5
6832
MA communication send error
Only MA Remote controller is detected.
E3/E5
6833
MA communication send error
Only MA Remote controller is detected.
E0/E4
6834
MA communication receive error
Only MA Remote controller is detected.
EF
7100
Total capacity error
EF
7101
Capacity code error
EF
7102
Connecting unit number error
EF
7105
Address setting error
EF
7130
Incompatible unit combination
Notes:
1. When the outdoor unit detects No ACK error/No response error, an object indoor unit is treated as a stop, and not assumed to be abnormal.
2. Refer to the service manual of indoor unit or remote controller for the detail of error detected in indoor unit or remote controller.