Check code
Abnormal points and detection methods
Causes and checkpoints
If no rotational frequency is detected, or detected a value outside the
specified range during fan motor operation.
Malfunction of fan motor
Disconnection of CNF connector
Defective outdoor multi controller circuit board
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
4400
(U8)
Fan trouble (Outdoor unit)
Notes:
Set SW7-1 OFF after the troubleshooting completes.
The fan sometimes starts on-off cycle operation during low-load
operation or cooling at low outside temperature. It is not abnormal;
the operation ensures reliability of the product.
No
No
Yes
Yes
Yes
No
Has the fuse melted?
Is there any abnormality such
as disconnection, looseness or
breakage?
Is the voltage normal?
• Replace the outdoor multi controller circuit board.
• Replace the defective fan motor.
Connect the wiring/connector properly.
Replace it in the case of breakage.
Replace the outdoor multi controller circuit
board.
Replace the defective fan motor.
Check the fuse on the outdoor multi
controller circuit board.
Check the fan motor connector (CNF1 and
CNF2) for disconnection or looseness.
(melted)
(Not melted)
1
While the breaker is OFF, disconnect the compressor
wirings (U/V/W) from the outdoor power circuit board
.
2
While the breaker is OFF, disconnect the fan motor
connector CNF1 and CNF2.
3
When 5 minutes have passed since turning ON the
breaker, turn SW7-1 ON.
4
Check the voltage of the outdoor multi controller circuit board.
Test points are;
· VDC approx. 310 to 350 VDC (fan connector 1–4)
· VCC approx. 15 VDC (fan connector 5–4)
· VCC approx. 0–6.5 VDC (fan connector 6–4)
64
65
TCH091