Check code
1302
(UE)
High pressure trouble or
High compressor temperature trouble
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Chart 4 of 4
Yes
Is there refrigerant leak?
Repair the refrigerant leakage.
No
(no leak)
Yes
Do 63H and TRS disconnect or loose ?
Reconnect 63H and TRS tightly.
No
No
No
Yes
No
Yes
Yes
Continued from the previous page.
Is the voltage detected?
Replace the SV1.
Replace the 63HS.
Replace the outdoor multi controller circuit
board.
Is the connector for outdoor
multi controller circuit board 63H
disconnected or loose?
Reconnect the connector or connect it tightly.
Check the 63HS voltage.
Is the resistance detected?
48
49
TCH091