Permissible Lengths
Constraint items
Indoor/outdoor transmission line
Maximum distance:
L
1
+ L
2
[
200 m (1.25 mm²)
MA remote controller cable length:
R
1
,
R
2
[
200 m (0.3 to 1.25 mm²)
Indoor/outdoor transmission line
Maximum distance:
L
1
+ L
2
[
200 m (1.25 mm²)
MA remote controller cable length:
R
3
+
R
4
,
R
5
[
200 m
(0.3 to 1.25 mm²)
Indoor/outdoor transmission line
Maximum distance:
L
1
+ L
2
[
200 m (1.25 mm²)
MA remote controller cable length:
R
6
+
R
7
[
200 m (0.3 to 1.25 mm²)
The MA remote controller and the M-NET remote controller cannot be used together with
the CITY MULTI series indoor unit of the same group.
M-NET remote controller cannot be connected without address setting.
3 MA remote controllers or more cannot be connected with the CITY MULTI series
indoor unit of the same group.
The second MA remote controller is connected with the terminal block (TB15) for the
MA remote controller of the same CITY MULTI series indoor unit (M-IC) as the first MA
remote control.
NO
MA-RC
(00)
M-IC
(00)
OC
MA-RC
(00)
M-IC
TB5
1 2
TB15
A B
M1 M2
TB3
S
TB7
TB5
TB15
M1 M2 S
M1 M2 S
1 2
M1 M2 S
A B
MA-RC
(Main)
TB5
TB15
(00)
M-IC
TB3
TB7
(00)
OC
TB5
TB15
(00)
M-IC
MA-RC
(Sub)
MA-RC
(Main)
MA-RC
(Sub)
MA-RC
(Main)
1 2
M1 M2 S
M1 M2 S
M1 M2 S
A B
A B
A B
A B
A B
1 2
M1 M2 S
NO
NO
TB5
TB15
TB3
TB7
(00)
OC
TB5
TB15
(00)
M-IC
MA-RC
MA-RC
M-NET RC
1 2
A B
M1 M2 S
M1 M2 S
M1 M2 S
1 2
M1 M2 S
A B
A B
(00)
M-IC
(00)
Содержание PUMY-P250YBM2-BS
Страница 23: ...23 TCH091 6 WIRING DIAGRAM ...
Страница 155: ......