108
OCH760
No.
SW1
setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678
1
2
3
4
5
6
7
8
53
10101
100
Outdoor LEV
-A
opening pulse
0–2000 (pulse)
Display of data at time of abnormality and abnormality delay
54
01
101
100
Outdoor LEV
-A opening
pulse abnormality delay
55
11
101
100
Outdoor LEV
-A opening
pulse abnormality
56
0001
1100
Outdoor LEV
-B
opening pulse
57
1001
1100
Outdoor LEV
-B opening
pulse abnormality delay
58
0101
1100
Outdoor LEV
-B opening
pulse abnormality
59
1101
1100
63LS (Low pressure)
−99.9–999.9 (Kgf/cm²)
Display of data from sensor
60
001
11
100
63LS abnormality delay
−99.9–999.9 (Kgf/cm²)
Display of data at time of abnormality and abnormality delay
61
101
11
100
63LS abnormality
62
011111
00
TH2 (HIC pipe)
−99.9–999.9 (°C)
Display of data from thermistor
63
111111
00
TH2 (HIC) abnormality delay
−99.9–999.9 (°C)
Display of data at time of abnormality and abnormality delay
64
00000010
TH2 (HIC) abnormality
65
10000010
Operational frequency
0–255 (Hz)
Display of actual operating frequency
66
01000010
Target frequency
0–255 (Hz)
Display of target frequency
67
11000010
Outdoor fan control
step number
0–15
Display of number of outdoor fan control steps (target)
68
00100010
Indoor LEV
Opening pulse
(No. 1 to 30 units)
0–2000 (pulse)
Address and display data are alternately displayed every second. Pressing SWP2 changes the
displayed unit in ascending order; it returns to No. 1 after No. 30.
69
10100010
High pressure sensor (Pd)
−99.9–999.9 (Kgf/cm²)
Display of detected data of outdoor unit sensors and thermistors
70
01
100010
TH4 (Compressor)(Td) data
−99.9–999.9 (°C)
71
11
100010
TH6 (Suction pipe) (ET) data
72
00010010
TH7 (Ambient) data
73
10010010
TH3 (Outdoor liquid pipe) data
74
01010010
TH8 (Heat sink) data
75
11010010
TH23 (Gas) data (No.
1 to 30 indoor units)
−99.9–999.9 (°C)
Address and display data are
alternately displayed every second. Pressing SWP2 changes the displayed unit
in ascending order; it returns to No. 1 after No. 30.
76
001
10010
TH22
(Liquid)
dat
a (
No.
1 to 30 indoor units)
−99.9–999.9 (°C)
77
101
10010
TH21 (Intake) data (No.
1 to 30 indoor units)
78
01
110010
Outdoor SC (cooling)
−99.9–999.9 (°C)
Display of outdoor subcool (SC) data
79
11
110010
Target subcool step
−2–4
Display of target subcool step data
80
00001010
Indoor SC/SH
(No. 1 to 30 units)
−99.9–999.9 (°C)
during heating: subcool (SC)/during cooling: superheat (SH) (Fixed to "0" during cooling operation)
Address and display data are alternately displayed every second. Pressing SWP2 changes the
displayed unit in ascending order; it returns to No. 1 after No. 30.