background image

ROOM AIR CONDITIONER

AWH120JE/123JE

AIR CONDITIONER

CONTENTS

1. Precautions

2. Product Specifications 

3. Installation and Operating 

Instructions

4. Disassembly and Reassembly

5. Troubleshooting

6. Exploded Views and Parts List

7. Block Diagram  

8. Wiring Diagram 

SERVICE

Manual 

THERMOSTAT

OPERATION

AWH120JE/~123JE front  4/8/98 9:27 AM  Page 1

Содержание AWH120JE

Страница 1: ...TIONER CONTENTS 1 Precautions 2 Product Specifications 3 Installation and Operating Instructions 4 Disassembly and Reassembly 5 Troubleshooting 6 Exploded Views and Parts List 7 Block Diagram 8 Wiring Diagram SERVICE Manual THERM OSTAT OPERA TION ...

Страница 2: ...ELECTRONICS Samsung Electronics Co Ltd MAR 1998 Printed in Korea Code No DB81 10151A 1 ...

Страница 3: ... cord and avoid tapping into a power cord This practice may result in malfunction or fire 6 After completing repairs and reassembly check the insulation resistance Procedure Prior to applying power measure the resistance between the power cord and the ground terminal The resistance must be greater than 30 megohms 7 Make sure that the grounds are adequate 8 Make sure that the installation condition...

Страница 4: ...rator Fan Fan Motor Compressor Rotary Overload Protect Compressor Capacitor Fan Motor Capacitor Fan Speed Control Thermo Control Unit of Measure mm mm Volt Hz A W FREON g BTU h BTU h W kg Row Type Row Type W Model µF VAC µF VAC AWH120JE 123JE COOL HEAT Window 600 X 394 X 555 699 X 441 X 638 220 240 Single 50 5 9 5 3 1 350 1 210 R 22 680 11 500 11 500 8 5 9 5 45 2 X 14 Propeller Fan 2 X 14 Blower A...

Страница 5: ...2 2 Dimensions 2 2 1 Main Unit 2 2 Samsung Electronics 600 395 395 595 Front view Side view Unit mm ...

Страница 6: ...e difference between the air inlet side and air outlet side should be 12 C at the minimum Standard state Indoor 27 C Outdoor 35 C 1 Check the refrigerant for leak 2 Check the evaporator condition freezing clogging with dust etc 3 Check whether the drain equipment DRAIN PAN DRAIN TUBE is installed The temperature difference between the air inlet side and outlet side should be 12 C at the minimum St...

Страница 7: ...6 Exploded View and Parts List 6 1 Main unit 6 1 Samsung Electronics 26 27 1 8 9 17 12 15 16 2 3 4 5 13 11 14 4 3 2 1 5 6 7 14 15 19 17 18 16 13 9 8 10 11 12 20 22 21 25 23 24 28 10 6 7 ...

Страница 8: ...1 1 12 DB90 50142A ASSY FRAME UP AWH120JE 1 1 13 DB96 30272A ASSY COND AWH120JE 1 1 14 DB63 10355A CAP DRAIN CR 1 1 15 DB90 20198A ASSY BASE AWH120JE 48F 1 1 16 DB27 10030B SOLENOID COIL ASS Y AWH090ZE 1 1 17 DB62 31722A TUBE CAPILLARY ASS Y ID 1 7 L1300 1 1 18 DB96 10591A ASSY TUB 4 WAY V V ASS Y 1 1 19 DB95 10062A ASS Y COMP 48H124JV1E4 1 1 20 DB72 50585A CLOTHE SOUND T35 1 1 21 DB60 30028A NUT ...

Страница 9: ...Samsung Electronics 6 2 Ass y Control 6 3 1 7 8 16 11 14 15 2 3 4 12 10 13 9 5 6 ...

Страница 10: ... 5 2501 001124 C OIL 3 5 30µF 450VAC 1 1 6 DB65 10100A CLIP CAPACITOR SECC P TO 8 1 1 7 DB95 20065F SWING MOTOR M2LJ49ZU32 1 1 8 DB47 20065A THERMOSTAT DEICE 3Pin 1 1 9 DB45 10009A TIMER DEFROST D2506 50Min 1 1 10 DB47 20060A THERMOSTAT BUA 129 1 1 11 DB34 90085A SELECTOR SWITCH 5PIN 7STEP 1 1 12 DB64 70081A PANEL CONTROL M HIPS 1 1 13 DB64 40169A INLAY CONTROL M AWH120JE 1 1 14 DB64 50138A KNOB T...

Страница 11: ...BRN SEESAW S W YEL RED SELECTOR S M PLUG GRN YEL GROUND BRN CAPACITOR DUAL RED BLU ORG RED GRN YEL RED BLK RED RED BLU YEL ORG GRN BLU RED GRN SKY BLU RED RED BLU BLU BLY THERMOSTAT DEICE DEICE TIMER SOLENOID COIL GRN 1 2 1 2 3 5 4 4 3 8 6 4 2 1 GRN YEL F M BLK WHT RED S C O L P BLK COMP THERMOSTAT BLU YEL RED BLU YEL ORG RED WHT YEL ORG BRN S L H M GRN 1 3 2 R ...

Отзывы: