8
OCH740
2-4. SYSTEM SPECIFICATIONS
(2) Method for identifying MULTI-S model
(1) Outdoor Unit
Outdoor unit <When using model 125 >
(3) Operating temperature range
Cooling
Heating
Indoor intake air temperature
W.B. 15 to 24°C
D.B. 15 to 27°C
Outdoor intake air temperature
D.B. −5 to 52°C
*1
W.B. −20 to 15°C
Notes:
D.B.:
Dry Bulb Temperature
W.B.:
Wet Bulb Temperature
*1
10 to 52°C D.B.: When connecting PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VKM, PFFY-P20/25/32VCM, PFFY-P20/25/32VLEM,
PFFY-P20/25/32VLRM(M), PEFY-P25/32/40VMA3-E; and M series, S series, and P series type indoor unit.
■ When connecting fresh air type indoor unit
• PEFY-P·VMH-E-F
Cooling
Heating
Indoor and Outdoor intake air temperature
D.B. 21 to 43°C
*2
W.B. 15.5 to 35°C
D.B.−10 to 20°C
*3
*2
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is lower than 21°C D.B..
*3
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is higher than 20°C D.B..
Temperature range is -5°C when the total of connecting capacity exceeds 100%.
• PEFY-P·VMHS-E-F
Cooling
Heating
Indoor and Outdoor intake air temperature
D.B. 17 to 43°C
*4
W.B. 15.5 to 35°C
D.B.−5 to 20°C
*5
*4
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is lower than 17°C D.B..
*5
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is higher than 21°C D.B..
■ When connecting PWFY unit
Cooling
Heating
Indoor intake water temperature
─
*6
D.B. 10 to 45°C
Outdoor intake air temperature
─
*6
W.B. −20 to 15°C
*6
• PWFY series can operate in Heating mode but not in Cooling mode. An indoor unit other than that of PWFY series can operate in
Cooling mode.
• A PWFY series and other series cannot operate simultaneously.
• The operation of PWFY series takes precedence over other series. While a PWFY series is operating, other series do not operate.
• The set temperature on the remote controller represents the target temperature of the outlet water.
Model
P112
P125
P140
Capacity
Cooling (kW)
12.5
14.0
15.5
Heating (kW)
14.0
16.0
18.0
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling
Indoor: D.B. 27°C/W.B. 19.0°C
Outdoor: D.B. 35°C
Heating
Indoor: D.B. 20°C
Outdoor: D.B. 7°C/W.B. 6°C
PU M Y
─
P
125
V K M
5 ─ BS
Outdoor unit
Refrigerant
R410A
MULTI-S
Frequency
conversion
controller
Indicates equivalent
to Cooling capacity(kcal/ h)
Power supply
V
: Single phase
220-230-240 V, 50 Hz
Outdoor unit
model type
M-NET
control
Sub
number
Salt proof
type