15
OCH740
Operation
PUMY-P112VKM5(-BS)
PUMY-P112VKM5-ET(BS)
PUMY-P112VKM5-ER(BS)
PUMY-P125VKM5(-BS)
PUMY-P125VKM5-ET(BS)
PUMY-P125VKM5-ER(BS)
PUMY-P140VKM5(-BS)
PUMY-P140VKM5-ET(BS)
PUMY-P140VKM5-ER(BS)
Operating
conditions
Ambient
temperature
Indoor
DB/
WB
27°C/19°C
20°C/—
27°C/19°C
20°C/—
27°C/19°C
20°C/—
Outdoor
35°C
7°C/6°C
35°C
7°C/6°C
35°C
7°C/6°C
Indoor unit
No. of connected units
Unit
2
2
2
No. of units in operation
2
2
2
Model
—
50 x 1/63 x 1
63 × 2
63 x 1/80×1
Piping
Main pipe
m
5
5
5
Branch pipe
2.5
2.5
2.5
Total pipe length
10
10
10
Fan speed
—
Hi
Hi
Hi
Amount of refrigerant
kg
7.2
7.2
7.2
Outdoor unit
Electric current
A
16.17
17.38
21.67
21.91
25.84
25.54
Voltage
V
230
230
230
Compressor frequency
Hz
67
69
84
86
96
96
LEV
opening
Indoor unit
Pulse
357
421
447
525
511
586
Pressure
High pressure/Low pressure
MPa G
2.70/0.94
2.86/0.70
2.86/0.88
2.87/0.67
2.95/0.85
2.95/0.65
Temp. of
each section
Outdoor
unit
Discharge
°C
67.0
71.9
69.7
72.1
70.7
73.2
Heat exchanger outlet
40.2
2.0
40.8
1.3
43.7
0.9
Accumulator inlet
8.7
1.0
8.0
0.2
5.6
−0.6
Compressor inlet
10.7
1.3
9.1
0.1
7.8
−0.7
Indoor unit LEV inlet
18.9
32.4
17.7
33.0
17.0
33.4
Heat exchanger inlet
12.3
55.5
11.1
55.7
10.4
56.8
4-3. STANDARD OPERATION DATA (REFERENCE DATA)
Содержание PUMY-P112VKM5-ERBS
Страница 25: ...25 OCH740 5 OUTLINES AND DIMENSIONS Unit mm ...
Страница 26: ...26 OCH740 6 WIRING DIAGRAM ...